Concentric Vent Termination - International comfort products C9MVX Installation Instructions Manual

90+ two-stage & two-stage, variable category iv, gas furnace
Table of Contents

Advertisement

Concentric Vent and Combustion−Air
Figure 27
Sidewall Termination
Combustion Air
Exhaust
Vent
Dimension "A" is touching or 2" (50.8mm) maximum separation.
Sidewall Inlet Vent and Exhaust−Air
Figure 28
Termination
"A"
Inlet
12, (304.8mm) Min.
Grade or Snow Level
Dimension "A" is touching or 2" (50.8mm) maximum separation.

Concentric Vent Termination

WARNING
!
CARBON MONOXIDE POISONING, FIRE AND
EXPLOSION HAZARD
Failure to follow this warning could result in
personal injury, death and/or property damage.
Inlet and outlet pipes may NOT be vented directly
above each other (standard vent terminals).
Concentric Vent Termination
Kit # NAHA001CV & NAHA002CV
For Concentric Vent Termination information call 931.270.4100
with the complete model and serial number of the furnace.
Refer to Special Venting Requirements for Installations in Canada
in the Vent and Combustion Air Connections Section.
These kits are for vertical or horizontal termination of the
combustion air inlet and the exhaust vent pipes on Category IV
gas−fired condensing furnaces. The NAHA001CV kit can be used
for 3" (76.2mm) diameter pipe systems. The NAHA002CV kit can
be used for 2" (50.8mm) diameter pipe system. Refer to Table 5
for the correct pipe size for the furnace. Both the combustion air
inlet and the exhaust vent pipes must attach to the termination kit.
The termination kit must terminate outside the structure and must
be installed per the instructions outlined below for vertical or
32
1, (25.4mm)
Maximum
Vent
"A"
25-22-02d
"A"
8, Min.
Exhaust
8, (457.2mm) Min.
204 (6.1m) Max.
18, (457.2mm) Min. for Cold Climates
[Sustained 05F(-175C) and below for
24 hours or more consecutive hours]
Specifications are subject to change without notice.
Sidewall Inlet Vent and Exhaust−Air
Figure 29
Termination with Exterior Risers
8, (203.2mm) Min.
204 (6.1m) Max.
Exhaust
"A"
Dimension "A" is touching or 2" (50.8mm) maximum separation.
Rooftop Inlet Vent and Exhaust−Air
Figure 30
Termination
Inlet
12, (304.8mm)
Min. Grade or
Snow Level
horizontal termination. Vertical termination is preferred. Field
supplied pipe and fittings are required to complete the installation.
Concentric Termination Kit
Table 5
NAHA001CV & NAHA002CV Venting
Table Dual Piping ONLY
40,000, 50,000, 60,000, & 75,000 Btuh Furnaces
NAHA002CV − 354 (10.7m) & (4) 90° elbows
with 2" (50.8mm) PVC pipe
80,000, 100,000 & 125,000 Btuh Furnaces
NAHA001CV − 35' (10.7m) & (4) 90° elbows
with 3" (76.2mm) PVC pipe
1. Do not include the field supplied 45° elbow in the total
elbow count.
2. If more than four elbows are required, reduce the length
of both the inlet and the exhaust pipes five feet for each
additional elbow used.
3. Elbows are DWV long radius type for 2
(76.2mm) vents.
NOTE: The minimum vent length is 54 (1.5m) of PVC. Feet of
pipe is whichever pipe run is the longest, either inlet or
outlet side.
If more than four elbows are required, reduce the length of
both the inlet and exhaust pipes 5' (1.5m)for each additional
elbow used.
8, (203.2mm) Min.
12, (457.2mm)
Min. Grade or
Inlet
Snow Level
"A"
18, (457.2mm) Min. for Cold Climates
[Sustained 05F(-175C) and below for
24 hours or more consecutive hours]
8, (203.2mm) Min.
204 (6.1m) Max.
Exhaust
18, (457.2mm) Min. for Cold Climates
[Sustained 05F(-175C) and below for
24 hours or more consecutive hours]
(50.8mm) and 3
"