PELLET STOKER KMP PX22 Contents Example: Power the burner. Pressing once causes the panel to ask “Start?”. Description ................2 Pressing again means that you confirm the question and the burner starts. Fitting ................3-4 If you turn one increment clockwise instead you jump in the main menu and come Electric installation .............5...
Screw feeder Allways observe the following: The PX22 stoker is to be mounted to one of the boiler hatches. The best place is The feeder inlet opening is not to be less than 100 mm from the bottom often where the oil burner normally goes, but if there is not sufficient room for the 150 mm from the nearest side wall of the storage bin.
Page 4
If temperature exceeds 60˚C there is little risk of condensation. clean, but most oil boilers are also suitable for PX22. If the stoker is to be installed in a combined wood and oil boiler, first find out if there is a big difference in stated If lower temperature, measures have to be taken.
PELLET STOKER KMP PX22 Electric installation Electric circut diagram All electric connections on the stoker and Fuses screw feeder have fast action connectors Thermal cut out 2 x 3,15 AT as below yellow/green 230 VAC 1. Power supply, fuses 2 x 3.15 AT...
PELLET STOKER KMP PX22 Start and setting Main menu First start Start? (Stop?) - Confirm by pressing once to start (stop). Start T - Press to select and adjust desired start temperature. The burner has default settings from the factory when delivered. It must be adjusted Stop T - Press to select and adjust desired stop temperature.
80˚C (recommended temperature) and the stoker stops. The cut-out thermostat must always be attached to the boiler! Two temperature sensors can be used with PX22. Simply connect two sensors via our junction box (accessories, art.no 1599) to the burner’s temp. sensor connector.
Safety systems fall out of the burner. To prevent this The PX22 stoker meets all current safety regulations and standards. you could mount the pellet retarder. There are two separate safety systems to avoid fire and hot gases going backwards:...
Page 9
PELLET STOKER KMP PX22 NOTE! Changing light sensor All work as described in the following text must be done by a qualified 1. Disconnect all three cables on the stoker. person. 2. Remove the burner cover by removing the two nuts and screws and pull the cover back.
Page 10
PELLET STOKER KMP PX22 Troubleshooting and repair Fault Cause What to do The burner stops Clean the burner and boiler. need(s) sweeping. Clean the burner and boiler. The burner stops, Fault code ErrSafe Reset the fall pipe’s overheat protection. Check the pellet supply and the The burner stops, starter dose “Ign dose”.
PELLET STOKER KMP PX22 Assemble description 1 Slacken off the screws holding the inner pipe. 2 Chose a suitable position for the feeder tube and fix it by means of the attached screws. CAUTION: the lower edge of the pipe must enter the inlet hole of the inner tube.
PELLET STOKER KMP PX22 Warranty For warranty issues Ariterm Sweden AB refers to our local Distributor. Installation Instructions - 2010.06.22 - 14/16...
Page 16
If these instructions are not followed during installation, operation and maintenance, the obligations of Ariterm Sweden AB under the warranty regulations are no longer binding. Ariterm reserve the right to alter any details and specifications without prior notice. Ariterm Sweden AB Flottiljvägen 15, SE-392 41 Kalmar...