7-7. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the right side of the
indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the
remote controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan runs at High
speed and the system is in continuous operation (The thermostat does not work).
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of
24°C. The fan speed shifts to Med..
In the test run or emergency operation, the horizontal vane operates in VANE AUTO (
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any
signal from the remote controller. In case of latter, normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
EMERGENCY OPERATION switch
This picture shows MSZ-GC22/25/35.
(Refer to "1. PARTS NAMES AND FUNCTIONS" for the other
models.)
7-8. 3-MINUTE TIME DELAY OPERATION
When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect
compressor from overload.
8

TROUBLESHOOTING

MSZ-GC22NA MSZ-GC25NA MSZ-GC35NA MSZ-GC50NA MSZ-GC60NA MSZ-GC71NA
8-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and after confirm-
ing the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the P.C. board.
3) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
The operation mode is indicated by the
Operation Indicator lamp as following
Operation Indicator lamp
Lead wiring
Housing point
18
) mode.
Operation mode
COOL
Set temperature
24°C
Fan speed
Med.
Horizontal vane
Auto
EMERGENCY COOL
EMERGENCY HEAT
STOP
HEAT
24°C
Med.
Auto
or
Lighted
Not lighted
or