Distance Between Cooktop And Ventilation Hood (S) - Miele DA398-6 Installation Instructions Manual

Table of Contents

Advertisement

de Mounting area (only d is required for recirculation hoods). Wall and ceiling
area for exhaust duct opening and for wall socket installation. Only the wall
socket installation is required for recirculation hoods.
Vent collar  6" (150 mm), with adapter  5" (125 mm).

Distance between cooktop and ventilation hood (S)

Provided a larger distance is not given by the manufacturer of the cooktop,
follow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INSTRUCTIONS" section.
Cooking appliance
Electric/Induction cooktop
Electric grill, deep fat fryer (electric)
Multi-burner gas cooktop
≤ 43,000 BTU/hr (12.6 W),
no burner > 15,000 BTU/hr (4.5 kW).
Multi-burner gas cooktop
≤ 73,800 BTU/hr (21.6 W),
no burner > 16,500 BTU/hr (4.8 kW)
Multi-burner gas cooktop
> 73,800 BTU/hr (21.6 W),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Single-burner gas cooktop
≤ 20,500 BTU/hr (6 kW)
Single-burner gas cooktop
> 20,500 BTU/hr (6 kW)
≤ 27,600 BTU/hr (8.1 kW)
Single-burner gas cooktop
> 27,600 BTU/hr (8.1 kW)
Installation
Minimum distance S
Miele
appliance
24" (610 mm)
26" (660 mm)
26" (660 mm)
30" (760 mm)
Not possible
26" (660 mm)
30" (760 mm)
Not possible
Non-Miele
appliance
30" (760 mm)
30" (760 mm)