External
Regulator
Figure 8 - External Regulator on Propane/LP Supply Tank with
Vent Pointing Down
Check your building codes for any special requirements for locating
equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent
excess sealant from going into pipe. Excess sealant in pipe could
result in clogged fireplace valves. Never use sealant on flare threads.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as
shown in Figure 9. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and fireplace.
Locate sediment trap where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This keeps them from
going into fireplace gas controls. If sediment trap is not installed or
is installed wrong, fireplace may not run properly.
Gas Shutoff
Valve
1/2" NPT Incoming
Gas Line
Note:
1) Wire connections not shown for clarity
2) * 1/8" NPT Plugged Tapping
8
INSTALLATION Continued
Propane/LP
Supply Tank
Vent
Pointing
Down
Inlet Pressure Tap
Flexible Gas Line
Do NOT Kink
Figure 10 - Connecting Incoming Gas Line to Flex Gas Line
SuperiorFireplaces.US.com
Equipment Shutoff
Valve With 1/8" NPT
Tap*
3" Minimum
Cap
Sediment Trap
* Purchase the optional equipment shutoff valve from your dealer.
** Minimum inlet pressure for purpose of input adjustment.
Figure 9 - Gas Connection
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1. Route flexible gas line (provided by installer) from equipment
shutoff valve to fireplace. Route flexible gas supply line through
one of the access holes on side of fireplace.
2. Attach flexible gas line from gas supply to control valve (see Figure
10).
3. Check all gas connections for leaks. See Checking Gas Connec-
tions, page 9.
Pilot Adjustment
Outlet Pressure Tap
Natural Gas
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
Pipe
Tee
Nipple Joint
Set Screw
127035-01C