The Fireplace JETMASTER 700 Installation Instructions Manual

Advertisement

Quick Links

Head Office & Showroom
12 Tawari St, Mt Eden, Auckland
0800 843 347 | 0800 The Fire
www.thefireplace.co.nz
JETMASTER GAS CONVECTOR INSTALLATION INSTRUCTIONS
ALL INSTRUCTIONS TO COMPLY WITH NZS5261:2003
Due to continued product improvement, The Fireplace Ltd reserves the right to change product specifications without prior notification
JETMASTER IGC BOX DIMENSIONS
Table 1
Model
A
700
700
850
850
1050
1050
1150
1200
1200
1300
1500
1500
1600
Dimensions in mm
Fig. 1
Front
IMPORTANT: Read all instructions carefully before starting installation. Failure to follow these
instructions may result in a fire hazard and will void the warranty.
This appliance must be serviced every 12 months by a registered gas fitter.
A TYPICAL IN-BUILT INTO TIMBER FRAMING
A1
A2
B
800
750
341
950
900
341
1100
341
1250
341
1550
341
Y
Gather
Convector
Box
Back
C
D
E
650
290
200/250
650
290
250/300
570
290
250/300
570
290
250/300
570
290
250/300
Fig. 2
Gather
C
D
4.G.4A
F
G
Y
630
265
235
630
265
235
550
265
235
550
265
235
550
265
235
E
B
A
A1
A2
G
F
9/2013

Advertisement

Table of Contents
loading

Summary of Contents for The Fireplace JETMASTER 700

  • Page 1 JETMASTER GAS CONVECTOR INSTALLATION INSTRUCTIONS A TYPICAL IN-BUILT INTO TIMBER FRAMING ALL INSTRUCTIONS TO COMPLY WITH NZS5261:2003 Due to continued product improvement, The Fireplace Ltd reserves the right to change product specifications without prior notification JETMASTER IGC BOX DIMENSIONS Table 1...
  • Page 2: Gas Input

    4.G.4B GAS TRAY OPERATING OPTIONS Table 2 SFB / DLX Manual *M.V. Wall Switch     1050   1200   1500   * M.V. - Millivolt: no electricity required GAS INPUT Table 3 Gas Input MJ/Hr MODEL 700 SFB 850 SFB...
  • Page 3: Margin Set

    4.G.4C CAVITY / FRAMING PREPARATION 1. Refer to the minimum framing dimensions as per Table 4 / Fig 3. Allow a temporary 1200mm lintel height, until the convector box and flue is installed. Install front nogs on edge to increase chimney chase dimension.
  • Page 4: Firebox Installation

    4.G.4D FIREBOX INSTALLATION 1. Fit and seal gather, using fire cement (exhaust cement) and bolts (supplied), to the convector box. Note: Pop rivet back of gather to convector box if required. 2. Locate and position convector box and gather in cavity. 3.
  • Page 5 4.G.4E PLAN Fig. 6 min 2 x 80mm diam. equal square or rectangle shape area wall or floor mounted air vents 6mm Hardiflex min 50mm from combust. material 6mm Hardiflex Rock-wool insulation Floor Protector RECESS PLAN Maximum Firebox Recess Value = 100mm Fig.
  • Page 6: Flue Installation

    Discuss Bird Proofing needs with your installer. N.B. in extreme wind areas it may be necessary to consult The Fireplace Ltd or your local agent for further technical assistance Ph: 0800 843 347. 10. If flue is concealed in a chase, allow for air vents (2 x 80mm diam. or equivalent) at the highest possible point on the chimney chase or alternatively, allow a min 25mm air space between the casing cover spigot and the outer casing.
  • Page 7: Minimum Height Of Flue System Exit

    4.G.4G FLUE PENETRATION Fig. 10 Typical Cowl Casing Cover EXTERNAL REQUIREMENTS Refer to NZS5261:2003 Top Spider Approved Flashing min. 25mm gap between flue pipe casing & combustible surface Air Vents min. 25mm dia. or equal flue pipe square or rectangle flue pipe casing Note: All external air vents &...
  • Page 8 4.G.4H CHIMNEY CHASE MINIMUM TRIM OUT Table 5 MODEL FLUE SYSTEM MINIMUM TRIM OUT DIMENSION X (min) Y (min) 200/250 250/300 1050 250/300 1200 250/300 1500 250/300 Dimensions in mm Note: A minimum 25mm clearance from flue pipe casing to combustible material must be maintained. Min.

This manual is also suitable for:

Jetmaster 850Jetmaster 1050Jetmaster 1200Jetmaster 1500

Table of Contents