The Fireplace Jetmaster Wood Installation Instructions Manual

Advertisement

Quick Links

4.R.1A
Jetmaster existing chimney
installation instructions - WooD / gas
WOOD INSTALLATION TO COMPLY WITH AS/NZS2918:2001
GAS INSTALLATION TO COMPLY WITH NZS5261:2003
imPortant: read all instructions carefully before starting installation. Failure to
follow these instructions may result in a fire hazard and will void the warranty.
7/2013

Advertisement

loading

Summary of Contents for The Fireplace Jetmaster Wood

  • Page 1 4.R.1A Jetmaster existing chimney installation instructions - WooD / gas WOOD INSTALLATION TO COMPLY WITH AS/NZS2918:2001 GAS INSTALLATION TO COMPLY WITH NZS5261:2003 imPortant: read all instructions carefully before starting installation. Failure to follow these instructions may result in a fire hazard and will void the warranty. 7/2013...
  • Page 2 Jetmaster Box Dimensions 4.R.1B Solid Fuel Box Dimensions Table 1. MODEL 700 SH 700 SH L 700 D 850 L 1050 1050 1150 1100 1050 LL 1050 1150 1100 Dimensions in mm Gas Convector Box Dimensions Table 2. MODEL 1050 1050 1150 1100 Dimensions in mm Gas Tray - MJ/Hr Ratings...
  • Page 3 Any surround or mantle must be installed as per the Fig 6, 7 and 8. Ensure there is at least 100mm clearance from the fireplace opening to any combustibles. If a cast iron fascia is fitted over the front of...
  • Page 4 Plan View - 4.R.1D Step 1 Fig. 1 Plan View - Step 2 Fig. 2 Solid bricks and/or Hebel block plastered or glue together mortar demolish and clean opening width maybe increased to suit Plan View - Step 3 Fig. 3 min 25 min 25 do not block chimney ports...
  • Page 5: Cross Section

    Cross Section 4.R.1E Tested to AS/NZS 2918:2001 Appendix E Fig. 4 Fit with optional cowl (recommended) Bird Proof if required mortar Rock Wool do not block chimney ports Lintel mortar top, back & sides of firebox Rock wool to seal Solid bricks and/or Hebel block plastered or glued together Maintain the air intake unobstructed...
  • Page 6: Clearances To Combustible Mantels

    Minimum Floor Protector 4.R.1F Table 4. MODEl Min. Depth* Fig. 5 Solid Fuel Models 440 U 500 U 600 U 1000 600 L 1000 700 SH 1100 700 SH L 1100 700 D 1100 850 U 1250 850 L 1250 1050 LL 1450 Gas Models 1100...
  • Page 7 25 min 25 Surround Leg max. recess = 100mm min 300 Combustible Side Wall Note: Always allow 100mm margin from opening of firebox to combustibles. Adjacent combustible side walls must be located a minimum 300mm from the fireplace opening.
  • Page 8 Air Replacement 4.R.1H The Fireplace Ltd recommends that allowances are made for air replacement vents to be located near the fireplace, to aid combustion and reduce the incidence of back venting. Refer to Table 5. for air vent sizing and suggested location. Fig. 9 - Location points A,B,C,D are suggested combinations. A minimum of one pair of air vents is recommended or one large vent, as per location point D.