GAS SUPPLY

The gas pipeline can be brought in through the vent-end of the
fireplace only. Consult the current National Fuel Gas Code, ANSI
Z223.1 installation code.
RECOMMENDED GAS PIPE DIAMETER
SCHEDULE 40 PIPE
TUBING, TYPE L
INSIDE DIAMETER
OUTSIDE DIAMETER
PIPE
LENGTH
(Dimensions in Inches)
NAT
LP
NAT
0-10 feet
1/2
3/8
1/2
10-40 feet
1/2
1/2
5/8
40-100 feet
1/2
1/2
3/4
100-150 feet
3/4
1/2
7/8
NOTICE: Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.
NOTICE: Since some municipalities have additional local codes,
it is always best to consult your local authority and installation
code.
The use of the following gas connectors is recommended:
— ANSI Z21.24 Appliance Connectors of Corrugated Metal
Tubing and Fittings.
— ANSI Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a
flexible appliance connector cannot exceed three feet in length.
TOP
2"
SHUT-OFF VALVE
8-3/4"
INCLUDED IN
ENVELOPE PACK
FRONT
2"
8-3/4"
Figure 12
Page 16
GAS SUPPLY PRESSURE (INCHES W.C.)
MINIMUM
NORMAL
Natural Gas
4.5
7.0
LP (Propane)
10.8
11.0
Manifold Pressure (inches w.c.)
LP
Normal (HI)
3/8
Natural Gas
3.5
1/2
LP (Propane)
10.0
1/2
3/4
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required
by the National Fuel Gas Code that a drip leg be installed near
the gas inlet. See Figure 13. This should consist of a vertical
length of pipe tee connected into the gas line that is capped
on the bottom in which condensation and foreign particles may
collect.
Figure 13
Figure 14
MAXIMUM
14.0
14.0
NOTICE: Island and Room Divider installation is possible as long as the horizontal portion of the vent system does not exceed 20 feet
with a minimum vertical run of 8 feet from fireplace floor. See details in Venting Section.
NOTICE: Inuslate to applicable codes when installing this fireplace against an exterior wall.
A minimum clearance of 6 inches must be maintained from the perpendicular wall to the firebox opening of the fireplace, if the fireplace
is installed in the room divider or peninsula room divider positions.
36092-2-0316
36092-2-0316

LOCATING FIREPLACE

Figure 15
Page 17