TROUBLESHOOTING
1. FREQUENT NUISANCE ALARMS OCCUR:
(1) Close kitchen / bathroom door when in use.
(2) Ensure that the alarm is sited at least 6m away from sources
of fumes.
(3) Contamination from insects, paint or paint fumes may have
occurred. Clean the alarm - see "User Instructions" leaflet.
(4) If the problem persists, resiting of the unit should be consid-
ered.
2. ALARM SOUNDS FOR NO APPARENT REASON:
(1) Identify the alarm source. On interconnected units, the red
light on the cover will flash rapidly only on the unit which is
the source of the alarm.
(2) Check for fumes, steam etc. from the kitchen or bathroom.
Paint and other fumes can cause nuisance alarms.
(3) Press the test/hush button to silence the Smoke/Heat Alarm
for 10 minutes.
(4) If alarm does not stop, switch off mains and remove unit (see
figure 1).
(Only remove alarm with red light flashing, the others are
probably satisfactory).
3. LOW BATTERY & OTHER BEEPS:
(On Ei144/146 only)
If the battery is correctly connected and the unit has beeped for
over 20 minutes the battery is probably depleted. Obtain a new
battery, disconnect the mains, then remove the alarm and re-
place the depleted battery.
(On Ei164/166 only)
Check the green mains power light is on. If not, check fuse, cir-
cuit breakers and wiring connections. If the green light is off, the
lithium cells will deplete after some months without mains and
will need to be recharged. If the above fails to turn on the green
light, a fault may exist. Switch off mains and remove the unit
(see figure 1).
(All Alarms)
(1) If the green mains light is on and replacing battery, recharg-
ing lithium cells or cleaning unit has not stopped beeps, a
fault may exist. Disconnect the mains first and replace the
unit (see figure 1).
P/N B13729 Rev 1
14
EI Electronics 2001
©
-230V AC SMOKE & HEAT ALARMS
IONISATION
HEAT
RECHARGEABLE LITHIUM CELL BACK-UP
EI
EI
161
164
ALKALINE 9 VOLT BATTERY BACK-UP
EI
EI
141
144
NO BATTERY BACK-UP
EI
EI
140
143
LEAVE WITH USER
SITING & INSTALLATION
INSTRUCTIONS
READ THIS FIRST
IDEALLY INSTALL IN THE CENTRE OF CEILING AT
4
LEAST 0.5m FROM LIGHT FITTINGS.
REMOVE UNIT FROM MOUNTING PLATE BY RELEASING
4
CATCH AS SHOWN IN FIG 1a.
Ei144/146 ONLY: CHECK BATTERY IS CONNECTED TO
4
SNAP (SEE FIG 1b). BATTERY WILL NOT POWER THE
UNIT UNTIL IT IS SNAPPED ON TO THE MOUNTING
PLATE.
ENSURE HOUSE LIVE MAINS IS CORRECTLY CON-
4
NECTED TO L TERMINALS ON ALL INTERCONNECTED
ALARMS - OTHERWISE UNITS WILL BE DAMAGED.
8
DO NOT FIT ACTUAL ALARM UNTIL ALL BUILDING WORK
IS COMPLETED TO AVOID CONTAMINATION. AFTER
CHECKING OPERATION, COVER SMOKE ALARM WITH
DUST COVER UNTIL REQUIRED FOR USE.
8
DISCONNECT THE ALARM BEFORE APPLYING HIGH
VOLTAGE TO HOUSE WIRING.
PAGE 14 & 1