[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 1.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
(5) Address setting method
Proce-
Unit or controller
dures
1
Indoor unit
2
LOSSNAY
3
MA
remote con-
troller
4
Outdoor unit
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
HWE0716A
Address
setting
range
Main
IC
01 to 50
unit
Sub unit
LC
01 to 50
Main
MA
No
remote
settings re-
control-
quired.
ler
Sub
MA
Sub
remote
remote
control-
controller
ler
OC
51 to 100
OS
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block (TB5) on LOSSNAY (LC). (Non-po-
larized two-wire)
Interlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Re-
fer to "4 [3] Entering the Interlock Settings into the MA
Remote Controller" or the installation manual for the MA
remote controller for the setting method.)
5) Switch setting
Address setting is required as follows.
Setting method
Assign the smallest ad-
To perform a group opera-
dress to the main unit in the
tion of indoor units that
group.
have different functions,
designate the indoor unit
Assign sequential numbers
in the group with the great-
starting with the address of
est number of functions as
the main unit in the same
the main unit.
group +1. (Main unit ad-
dress +1, main unit ad-
dress +2, main unit
address +3, etc.)
Assign an arbitrary but
None of these addresses
unique address to each of
may overlap any of the in-
these units after assigning
door unit addresses.
an address to all indoor
units.
-
Settings to be made ac-
cording to the remote con-
troller function selection
Assign sequential address
To set the address to 100,
to the outdoor units in the
set the rotary switches to
same refrigerant circuit.
50.
The outdoor units are auto-
matically designated as OC
and OS.(Note)
- 29 -
29
Factory
Notes
setting
00
00