[ IX Troubleshooting ]
Items to be checked
[3]
(1)
Disconnect the inverter
Check whether
output wire from the out-
the inverter is
put terminals (U, V, W) of
damaged.
the IPM.
(No load)
(2)
Turn on SW1-1 on the in-
verter board.
(3)
Put the outdoor unit into
operation.
[4]
Put the outdoor unit into oper-
Check whether
ation.
the inverter is
Check the inverter output volt-
damaged.
age after the inverter output
(During com-
frequency has stabilized.
pressor opera-
tion)
[5]
Remove the wire for the out-
Check the fan
door fan motor, and check the
motor ground
fan motor megger and the
fault or the
winding resistance.
winding.
[6]
(1)
Check the fan output wir-
Check the Fan
ing.
board failure.
(2)
Check the connector CN-
VDC connection.
(3)
Check the Fan board fail-
ure.
HWE0716A
Phenomena
1)
Inverter-related problems are de-
tected.
2)
Inverter voltage is not output.
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
4)
There is no voltage imbalance be-
tween the wires.
1)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
1)
Fan motor megger failure
Failure when the megger is 1Mohm
or less.
2)
Fan motor disconnection
Standard: The winding resistance
is approximately several ohm.
(It varies depending on the temper-
ature, or while the inner thermo is
operating, it will be
ohm)
Connector contact failure
Board side (CNINV)
Fan motor side
Cnnector contact failure
1)
The voltage imbalance among
each motor wiring during operation
(The voltage imbalance is greater
than the larger of the values repre-
sented by 5% or 5 V.)
2)
The same error occurs even after
the operation is restarted.
- 199 -
Remedy
Turn off SW1-1 and go to [1]
Check the connection be-
tween the IPM and the
CNIPM on the INV board.
Replace the IPM.
If the problem persists, re-
place the INV board.
Replace the IPM.
If the problem persists, re-
place the INV board.
Normal
*Turn off SW1-1
Replace the IPM.
If the problem persists, re-
place the INV board.
If the problem persists after
replacing the above parts, go
to section [2].
Replace the fan motor.
Connect the connector.
Connect the connector.
Replace the Fan board.
GB