[ VIII Test Run Mode ]
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected units
Indoor
No. of units in operation
unit
Model
Operating
conditions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
SC (LEV1)
LEV open-
ing
LEV2
LEV4
High pressure (after O/S)/low pres-
Pressure
sure (before accumulator)
Discharge (TH4)
Heat exchanger outlet
(TH3)
Outdoor
Accumulator inlet
unit
Temp. of
Accumulator outlet
each sec-
tion
Compressor inlet
Compressor shell bottom
LEV inlet
Indoor
unit
Heat exchanger outlet
HWE0716A
Operation
DB/WB
Unit
m [ft]
[lbs-oz]
Hz
Pulse
MPa
[psi]
°C [°F]
Outdoor unit model
PUHY-HP192TSHMU-A
PUHY-HP96THMU-A
21.1°C/ - [70°F/ - ]
8.3°C/ 6.1°C [47°F/43°F]
-
-
kg
A
V
72
0
2.81/0.66 [408/96]
84 [183]
-3 [26]
-3 [26]
-3 [26]
-3 [26]
40 [104]
- 114 -
PUHY-HP96THMU-A
4
4
140/140/140/140
5 [16-3/8 ]
10 [32-3/4 ]
45 [147-5/8]
Hi
26.4 [58-5/16]
49.2
230
72
406/406/406/406
0
1400
0
2.81/0.66 [408/96]
84 [183]
-3 [26]
-3 [26]
-3 [26]
-3 [26]
40 [104]
37 [99]
80 [176]