8.2 Clearances to Walls and Ceiling

The clearances to combustible walls may be slightly different in Canada and the U.S.A.
and may also differ depending on whether you use single or double wall flue pipe. Please
be sure to choose the correct clearance for your location and type of flue pipe. See figure
Clearances to combustible materials and floor protection to match each letter to a
clearance.
APPLIANCE CLEARANCES
(INSTALLATION WITH SINGLE
WALL PIPE CONNECTOR)
CANADA
A
15½" (394 mm)
B
18" (457 mm)
C
10" (254 mm)
K
48" (1220 mm)
L
84" (213 cm)
Note: These clearances are also valid for an alcove installation.
If the above clearances are met, then the distances measured from the flue outlet
will be:
DISTANCES* FROM PIPE
CONNECTOR TO THE
COMBUSTIBLE MATERIALS
CANADA
D
18" (457 mm)
E
26¼" (667 mm)
F
18" (457 mm)
*The pipe distances listed in this table refer to the distances obtained when the
stove is installed in accordance with the appliance clearances above mentioned.
However, you can install the stove at reduced clearances; follow the instructions in
Section 8.4: Reducing Wall and Ceiling Clearances Safely. Where they are followed,
the new distance of the pipe to combustible materials must be respected in the
appropriate certification of the pipe.
USA
15" (381 mm)
18" (457 mm)
10" (254 mm)*
48" (1220 mm)
84" (213 cm)
USA
17½" (455 mm)
26¼" (667 mm)
18" (457 mm)
APPLIANCE CLEARANCES
(INSTALLATION WITH DOUBLE
WALL PIPE CONNECTOR)
CANADA
A
10" (254 mm)
B
18" (457 mm)
C
10" (254 mm)
K
48" (1220 mm)
L
84" (213 cm)
DISTANCES* FROM PIPE
CONNECTOR TO THE
COMBUSTIBLE MATERIALS
CANADA
D
12½" (318 mm)
E
26¼" (667 mm)
F
18" (457 mm)
USA
10" (254 mm)
18" (457 mm)
10" (254 mm)
48" (1220 mm)
84" (213 cm)
USA
12½" (318 mm)
26¼" (667 mm)
18" (457 mm)
35