Download Print this page

Mitsubishi Electric PUZ-A12NHA Installation Manual page 6

Hide thumbs Also See for PUZ-A12NHA:

Advertisement

Available languages

Available languages

4.
Installing the refrigerant
piping
(_) Stop valve <Liquid side>
(_) Stop valve <Gas side>
C-C) Service
port
(_) Open/Close
section
®
®
Local pipe
_F_Sealed, same way for gas side
_) Pipe cover
CH_ Do not use a wrench
here.
Refrigerant
leakage
may result.
Ci_Use two wrenches
here.
4.4. Refrigerant pipe airtight
testing
method
(1) Connect the testing tools.
.
Make sure the stop valves @ _) are closed and do not open them.
.
Add pressure to the refrigerant
lines through the service port © of the liquid
stop valve (_.
(2) Do not add pressure to the specified pressure all at once; add pressure little by little.
Pressurize
to 0.5 MPa (5 kgf/cm2G), wait five minutes, and make sure the
pressure does not decrease.
Pressurize
to 1.5 MPa (15 kgf/cm2G), wait five minutes,
and make sure the
pressure does not decrease.
(_ Pressurize
to 4.15 MPa (41.5 kgf/cm2G) and measure the surrounding
tem-
perature and refrigerant pressure.
(3) If the specified pressure holds for about one day and does not decrease, the pipes
have passed the test and there are no leaks.
.
If the surrounding
temperature
changes
by 1 °C, the pressure will change by
about 0.03 MPa (0.3 kgf/cm2G). Make the necessary
corrections.
(4) If the pressure
decreases
in steps (2) or (3), there is a gas leak. Look for the
source of the gas leak.
(1)
(2)
Fig. 4=4
®
®
®
®
Type A
Type B
Fig. 4-5
®
4.5. Stop valve opening
method
(1) Gas side of A24-A42 (Fig. 4-5)
Type A
Remove the cap, then turn one-quarter rotation counter-clockwise
with a flat-bladed
screwdriver
to complete open.
Check that the valves are fully open, then return the cap to its original state and
tighten it down.
Type B
Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock-
wise direction to open.
Make sure that the stop valve is open completely,
push in the handle and rotate
the cap back to its original position.
(2) Liquid side of A24-A42 and Gas/Liquid
side of A12, A18 (Fig. 4-6)
Remove the cap and turn the valve rod counterclockwise
as far as it will go with
the use of a 4 mm hexagonal
wrench. Stop turning when it hits the stopper.
(06.35,
1/4 inch: Approximately
4.5 revolutions)
(e9.52, 3/8 inch: Approximately
10 revolutions)
Make sure that the stop valve is open completely,
push in the handle and rotate
the cap
back
to its original
position.
(_) Valve
(_) Unit side
CO) O peration
section
(_ Cap
Local pipe side
(_ Pipe cover
(G'_ S ervice
port
(_ Wrench
hole
Ci_Double spanner section
(Do not apply a spanner
other than to this sec-
tion. Doing so would cause coolant leaks.)
_3_Seal section
(Seal the end of the heat insulation
material at
the pipe connection
section with whatever seal
material you have on hand so that water does
not infiltrate the heat insulation
material.)
(K_Handle
Refrigerant
pipes are protectively
wrapped for A24-A42
. The pipes can be protectively
wrapped up to a diameter of e90 mm, 3-35/64 inch
before or after connecting
the pipes. Cut out the knockout in the pipe cover follow-
ing the groove and wrap the pipes.
Pipe inlet gap for A24-A42
. Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain.
(If the gaps are not closed, noise may be emitted or water and dust will enter the
unit and breakdown
may result.)
4.6. Addition of refrigerant
. Additional
charging is not necessary
if the pipe length does not exceed 20 m, 70 ft
for A12-A36, 30 m 100 ft for A42.
. If the pipe length exceeds the specified
length above, charge the unit with addi-
tional R410A refrigerant according to the permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional
refrigerant through
the liquid stop valve after the pipe extensions
and indoor
unit have been
vacuumized.
When the unit is operating,
add refrigerant
to the gas check valve using a
safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant,
note the added refrigerant amount on
the service label (attached to the unit).
Refer to the "1.5. Using R410A refrigerant
air conditioners"
for more informa-
tion.
Be careful when installing multiple units. Connecting to an incorrect indoor unit can
lead to abnormally
high pressure and have a serious effect on operation perform-
ance.
Additional
refrigerant charging amount (kg/oz)
Model
Max pipe
Max height
20 m
25 m
27 m
30 m
33.5 m
36.6 m
40 m
43 m
45.5 m
48.8 m
50 m
length
difference
70 ft
80 ft
90 ft
100 ft
110 ft
120 ft
130 ft
140 ft
150 ft
160 ft
165 ft
O.06kg
0.11kg
0.17kg
A12, A18
30m,
lOOft
30m,
lO0ft
0
2oz
4oz
6oz
....
0.17 kg
0.34 kg
0.51 kg
0.68 kg
0.85 kg
1.02 kg
1.19 kg
1.36 kg
1.53 kg
1.70 kg
A24, A30, A36
50 m, 165 ft
30 m, 100 ft
0
6 oz
12 oz
18 oz
24 oz
30 oz
36 oz
42 oz
48 oz
54 oz
60 oz
0.17 kg
0.34 kg
0.51 kg
0.68 kg
0.85 kg
1.02 kg
1.19 kg
A42
50 m, 165 ft
30 m, 100 ft
0
0
0
0
6 oz
12 oz
18 oz
24 oz
30 oz
36 oz
42 oz
6

Hide quick links:

Advertisement

loading