7. Test run
7.2. Test run
7.2.1.
Using
SW4
in outdoor
unit
1) PUHType,
PUZType
SW4-1
ON
SW4-2
OFF
Cooling operation
SW4-1
ON
SW4-2
ON
Heating operation
2) PUY Type
SW4-1
ON
OFF
SW4-2
ON or
Cooling operation
* After performing
the test run, set SW4-1 to OFR
* After power is supplied, a small clicking noise may be heard from the inside of the outdoor
unit.The electronic expansion valve is opening and closing.The unit is not faulty.
A few seconds after the compressor
starts, a clanging noise may be heard from the
inside of the outdoor unit.The noise is coming from the check valve due to the small
difference
in pressure in the pipes. The unit is not faulty.
The test run operation
mode cannot be changed
by DiP switch
SW4-2 during
the test run. (To change
the test run operation
mode during
the test run, stop
the test run by DIP switch
SW4-1. After changing
the test run operation
mode,
resume the test run by switch
SW4-1 .)
7.2.2. Using remote controller
Refer to the indoorunit installation manual.
8. Special
Functions
®
®
©
©
i
i
Red
i
,
i
i
Brown
I
'
"
,
L
®
Fig. 8-1
@ Circuit diagram example (low noise mode)
@ Outdoor
unit control board
_p On-site arrangement
_ Max. 10 m, 33 ft
© External
input adapter
(PAC-SC36NA)
8.1. Low noise mode (on-site modification)
(Fig. 8-1)
By performing
the following
modification,
operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated
when a commercially
available
timer or the
contact input of an ON/OFF
switch is added to the CNDM connector
(option) on the
control board of the outdoor unit.
The capacity may be insufficient according
to the outdoor temperature
and condi-
tions, etc.
(_) Complete
the circuit
as shown
when using the external
input adapter
(PAC-
SC36NA). (Option)
®
SWl ON: Low noise mode
SWl OFF: Normal operation
8.2. Refrigerant
collecting
(pump down)
Perform the following procedures
to collect the refrigerant
when moving the indoor
unit or the outdoor unit.
L_ Before collecting the refrigerant, first make sure that the all of the SW5 DIP switches
for function changes on the control board of the outdoor unit are set to OFE If all of the
SW5 switches are not set to OFF, record the settings and then set all of the switches
to OFE Start collecting the refrigerant. After moving the unit to a new location and
completing the test run, set the SW5 switches to the previously recorded settings.
Supply power (circuit breaker).
* When power is supplied, make sure that "CENTRALLY
CONTROLLED"
is not
displayed
on the remote controller.
If "CENTRALLY
CONTROLLED"
is dis-
played, the refrigerant collecting (pump down) cannot be completed
normally.
(_ After the gas stop valve is closed, set the SWP switch on the control board of the
outdoor
unit to ON. The compressor
(outdoor unit) and ventilators
(indoor and
outdoor units) start operating
and refrigerant
collecting
operation
begins. LED1
and LED2 on the control board of the outdoor unit are lit.
* Only set the SWP switch (push-button
type) to ON if the unit is stopped. How-
ever, even if the unit is stopped and the SWP switch is set to ON less than
three minutes after the compressor
stops, the refrigerant collecting operation
cannot be performed. Wait until compressor
has been stopped for three min-
utes and then set the SWP switch to ON again.
Because the unit automatically
stops in about two to three minutes after the refrig-
erant collecting operation
(LED1 and LED2 are lit), be sure to quickly close the
gas stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, open
the liquid stop valve completely,
and then repeat step (_) after three minutes have
passed.
* If the refrigerant collecting operation has been completed
normally (LED1 and
LED2 are lit), the unit will remain stopped until the power supply is turned off.
®
Turn off the power supply (circuit breaker).
9. System
control
(Fig. 9-1)
{E_SW1
-3-6
3456
_SWl-3-6ONoFF
3456
@swt-3-6
ON
OFF
E,
TB1
zq
(_) Outdoor
unit
(_ Indoor unit
{-C}Master remote controller
(_ Subordinate
remote controller
Standard
1:1 (Refrigerant
address = 00)
(_ Simultaneous
twin (Refrigerant
address = 01)
(G'_ Simultaneous
twin (Refrigerant
address = 02)
* Set the refrigerant
address using the DIP switch of the outdoor unit.
(_) Wiring from the Remote Control
This wire is connected
toTB5 (terminal board for remote controller)
of the indoor unit
(non-polar).
@} When a Different Refrigerant
System Grouping
is Used.
Up to 16 refrigerant
systems can be controlled
as one group using the slim MA re-
mote controller.
3456
___
TB1
I
Note:
In single
refrigerant
system
(twin/triple),
there
is no need of wiring
(_).
SW1
_
Function
Function table
1 Compulsory
de-
<SW1 >
frosting
SWl
2 Error history clear
ON_
function
3 Refrigerant
sys-
OFF_
settings
4 tern address
set-
5 ting
6
Operation accordingto switchsetting
ON
OFF
Start
Normal
Clear
Normal
Settings for outdoor unit ad-
dresses 0 to 15
Fig. 9-1
10

Hide quick links:

Advertisement

loading