Parameter
With heating circuit pump logic function:
address b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow
temperature limit 20 °C
(only for weather-com-
pensated control units)
C6:74
Electronic maximum flow
temperature limit 74 °C
(only for weather-com-
pensated control units)
d3:14
Heating curve slope =
1.4
d4:0
Heating curve level = 0
d5:0
The external heating pro-
gram changeover
changes the heating pro-
gram to "Constant opera-
tion with reduced room
temperature" or "Standby
mode" (only for weather-
compensated control
units)
d6:0
Heating circuit pump
stays in control mode at
signal "External block-
ing"
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
- 1 K
actual
set
> RT
- 2 K
actual
set
(cont.)
Heating circuit pump "ON"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d3:2
Heating curve slope adjust-
to
able from 0.2 to 3.5 (see
d3:35
page 33)
d4:–13
Heating curve level adjust-
to
able from –13 to 40 (see
d4:40
page 33)
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (subject to coding
address 3A, 3b and 3C)
d6:1
Heating circuit pump stops
at signal "External block-
ing" (subject to coding
addresses 3A, 3b and 3C)
Code 2
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
- 1 K
set
- 2 K
set
- 3 K
set
77