Solar/group "4"
Coding in the delivered condition
Cylinder maximum temperature
08:60
The solar circuit pump will
stop when the actual cyl-
inder temperature rea-
ches 60 °C (maximum
cylinder temperature).
Stagnation time reduction
0A:5
To protect the system
components and heat
transfer medium, the
speed of the solar circuit
pump is reduced when
the differential between
the actual cylinder tem-
perature and the set cyl-
inder temperature is less
than 5 K.
Flow rate solar circuit
0F:70
The flow rate of the solar
circuit at the maximum
pump speed is set to
7 l/min.
(cont.)
Possible change
08:10
The maximum cylinder
to
temperature can be adjus-
08:90
ted from 10 to 90 °C.
0A:0
The differential between
to
the set cylinder tempera-
0A:40
ture and the start point for
reducing the stagnation
time can be adjusted from
0 to 40 K.
0F:1
Flow rate of the solar circuit
to
adjustable from 0.1 to
0F:255
25.5 l/min
Code 1
45