Parts And Accessories - Honeywell HM700A1000 Installation Instructions Manual

Electrode steam humidifier
Hide thumbs Also See for HM700A1000:
Table of Contents

Advertisement

HM700A1000
MODEL:
S/N:
HM700A1000
LISTED
205X
HUMIDIFIER
PHASE:
HZ:
1
60
VOLTS 1:
F.L.A:
GPD:
110-120
12.0
11
KW:
VOLTS 2:
F.L.A:
GPD:
KW:
220-240
12.0
22
Golden Valley Minnesota 55422
DATE:
XXXXXXXXX
MADE IN CANADA
Auto-Adaptive
Fig. 1. Specification label location.
CAUTION
Servicing
Disconnect main power before any servicing.
The plumbing and electrical compartments contain
high voltage components and wiring. Access should
be limited to authorized personnel only.
During and following operation of the humidifier, the
steam and components in contact with the steam
such as the steam lines, steam distributors, and
condensate lines can become hot and can burn if
touched.
Honeywell does not accept any liability for installations
of humidity equipment installed by unqualified
personnel or the use of
parts/components/equipment that are not
authorized or approved by Honeywell.
To maintain warranty, only Honeywell approved parts
and cylinders may be used in the operation of the
product.

Parts and Accessories

The following parts and accessories are available and may have been included with your HM700 humidifier. The cylinder is the
only item that will need periodic replacement to maintain proper humidifier operation.
Replacement Cylinder
HumidiPRO Humidistat
Stainless Steel Distribution Remote Mount Kit
Replacement Drain Valve
Replacement Fill Valve
Replacement Transformer
Replacement PC Board
15 ft. Insulated Steam and Condensate Line Hose Kit
Differential Pressure Switch for Air Proving
33-00118—01
XXXXXXX
1.4
2.9
2583297A
Table 2. Parts and accessories.
Part/Accessory
CAUTION
Electrical
All electrical work should be done according to local
and national electrical code.
Electrical connection to be performed by a licensed
electrician.
Unit must be powered by a dedicated GFI circuit.
CAUTION
Plumbing
Plumbing to be performed by a licensed plumber.
Drain water from humidifier can be very hot. Do not
drain to public sink.
All plumbing work should be done according to local
plumbing code.
M35758
CAUTION
Installation
Do not mount on hot surfaces.
Do not mount in area where freezing can occur.
Do not mount on vibrating surface.
Do not mount on floor.
The HM700 produces steam at atmospheric pressure.
No devices which could block steam output should
be connected to the steam outlet.
Steam lines must be installed so that no restriction can
produce backpressure in the humidifier.
CAUTION
Water quality
The Honeywell HM700 requires a cold water
connection from your home's main water supply
between 30-100 PSIG. A throttle valve may be
necessary, and a water shut-off valve is
recommended for safety. Reverse Osmosis (RO)
and Deionized (DI) water must not be used. Water
conductivity is important to ensure the electrode
humidifier operates effectively. Honeywell
recommends 150-1200 μS (microsiemens).
HM700ACYL2
H6062A1000
HM700ADISTKIT
HM700ADVALVE
HM700AFVALVE
HM700ATX
HM700APCB
HM700AHOSEKIT
50027910-001