IMPORTANT: The common (COM) terminals from all
three fan coil relay boards must be connected to the 'P'
terminal in condensing unit 'A'.
Route thermostat cable or equivalent single leads of no. 18
AWG (American wire Gage) colored wire from subbase termi-
nals through conduit in unit to low-voltage connections as
shown on unit wiring diagram and Fig. 10A-10C.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated
wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insu-
lated wire (35 C minimum). For over 75 ft, use no. 14 AWG
insulated wire (35 C minimum). All wire larger than no. 18
AWG cannot be directly connected to the thermostat and will
require a junction box and a splice at the thermostat.
38AQS
Model
Name-
plate
501
208-230
012
601
460
101
575
501
208-230
016
601
460
101
575
38AQS
Model
Name-
plate
800
230
012
900
400
800
230
016
900
400
LEGEND
— Full Load Amps (fan motors)
FLA
ICF
— Maximum Instantaneous Current Flow during start-up
(LRA of compressor plus total FLA of fan motors)
LRA
— Locked Rotor Amps
— Minimum Circuit Amps per NEC Section 430-24
MCA
MOCP — Maximum Overcurrent Protection (fuse only)
RLA
— Rated Load Amps (compressor)
THERMOSTAT NO.
SUBBASE NO.
Type
Display — °F or °C
CCN Compatible
2 Cooling Stages
2 Heating Stages
Auto Changeover
Fan Switch
Timeclock
Emergency Heat
LEGEND
CCN — Carrier Comfort Network
*Thermostat kit includes Temp System relay pack.
†Subbase has ON-AUTO fan switch.
Table 7A — Electrical Data (3 Ph/60 Hz)
UNIT
Volts
Supplied*
MCA
Min
Max
187
253
62.5
414
528
29.1
518
660
22.8
187
253
87.5
414
528
40.7
518
660
33.0
Table 7B — Electrical Data (3 Ph/50 Hz)
UNIT
Volts
Supplied*
MCA
Min
Max
198
264
47.5
342
457
31.4
198
264
66.9
342
457
43.0
Table 8 — Recommended Thermostats
33CSTKT-01*
Communicating, Programmable
X
X
X
X
X
X
X
ELECTRIC RESISTANCE CRANKCASE HEATER — The
crankcase heater is inserted into the compressor crankcase. The
crankcase heater is operated from the normally closed contacts
of the control relay (CR1) and is automatically energized when
compressor stops. This heater keeps crankcase warm to pre-
vent oil dilution by refrigerant, ensures good lubrication, and
minimizes loss of oil during start-up.
AIRFLOW SWITCH — Carrier recommends an indoor air-
flow switch (field supplied) be installed and interlocked with
the outdoor unit. This prevents the outdoor unit from operating
if indoor airflow fails (broken fan belt, etc.). Operation of the
compressor in vacuum can damage bearing surfaces. Install
indoor airflow switch in a convenient location at the indoor
supply air duct and wire per Fig. 11.
COMPRESSOR
MOCP
ICF
(Amps)
RLA
Fuse Only
178
100
43.6
81
40
20.0
65
35
15.7
274
125
63.6
124
60
29.3
100
50
23.8
COMPRESSOR
MOCP
ICF
(Amps)
RLA
Fuse Only
134.4
75
32.9
80.4
50
20.0
206.4
100
47.9
121.4
60
29.3
*Units are suitable for use on electrical systems where voltage sup-
plied to the unit terminals is not below or above the listed limits.
NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electric Code) (U.S.A. Standard), Article 440.
2. Motor RLA and FLA values are established in accordance
with UL (Underwriters' Laboratories) Standard 1995 (U.S.A.
Standard).
33CSTK--01*
HH07AT172 (°F)
HH93AZ177†
X
X
X
X
X
X
11
FAN MOTORS (Single-Phase)
FLA (ea)
Total
Fan No.
LRA
Fans
1
170
4.3
77
2
2.3
62
1.8
266
4.3
120
2
2.3
96
1.8
FAN MOTORS (Single-Phase)
FLA (ea)
Total
Fan No.
LRA
Fans
1
128
3.5
2
74
3.5
200
3.5
2
115
3.5
HH07AT162 (°C)
HH93AZ177†
Standard
X
X
X
X
X
X
X†
X†
X
X
2
3.7
1.9
1.8
3.7
1.9
1.8
2
2.9
2.9
2.9
2.9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38aqs016

Table of Contents