FLUE TERMINAL POSITIONS
Th e fl ue discharge position for any fl ue type must conform to the following requirements
Fig 6.6
Minimum Distance
A Directly below an opening, air brick, opening window etc.
B Above an opening, air brick, opening window etc.
C Horizontally to an opening, air brick, opening window etc.
D Below a gutter or sanitary pipework
E Below the eaves
F Below a balcony or carport roof
G From vertical drain/soil pipework
H From an internal or external corner
I Above ground, roof or balcony level
J From a surface facing terminal
K From a terminal facing the terminal
L From a opening in a carport (e.g. door, windows) into the building
M Vertically from a terminal on the same wall
N Horizontally from a terminal on the same wall
NEOfl o Water Heater
16
mm
300
300
300
75
200
200
150
300
300
600
1200
1200
1500
300
September 2015