MODEL 91 BAY
MINIMUM CLEARANCES
The New Buck Corporation Model 91 Bay must be installed in compliance with instructions contained in this
manual.
Clearance from combustible walls and ceilings. (Using single wall chimney connector)
The minimum lateral distance between any part of room heater and combustible walls is shown in Figures 10 and 11
BACK WALL
BACK WALL
B
E
E
A
A
FIGURE 10
A
B
MODEL 91
24"
23"

FLOOR PROTECTION

If a freestanding model is to be installed on a combustible floor, a non-combustible pad must be placed under unit
to protect floor from burning material from the stove. The pad must be 50 inches wide. NOTE: The floor must
extend 16" from door opening in front of stove, 8" from door opening on each side of unit and should be under the
chimney connector. Floor protector must be 3/8" in minimum thickness, non-combustible material or equivalent.
NOTE: For clearance reductions using wall protectors, refer to the NFPA-211 Code.
TOOLS FOR INSTALLATION
Drop Cloth
Electric Drill with 7/32" drill bit
1/2" - 9/16" combination wrench
3/8" magnetic socket chuck adapter, 3/8" wrench (box or socket) or adjustable wrench
Socket Set
Tape Measure
Pencil
Level
Screw Driver
F
F
B
G
D
D
G
MINIMUM CLEARANCES
C
D
E
F
G
16" 26"
8"
3"
16"
Page 13
C
C
C
50"
FIGURE 11
C