A.O. Smith ADM - 40 Installation, User And Service Manual page 21

Commercial atmospheric water heater
Table of Contents

Advertisement

3.4.3
Gas data
Description II
2H3+
Gas category 2H: General
Orifice diameter
(1) = Blank plate
(2) = Burner pressure regulator
(3) = High/low regulator
Gas category G20 - 20 mbar
Nominal load (gross calorific value)
Nominal output
Supply pressure
Burner pressure
(*)
Gas consumption
Emissions of Nitrogen Oxides (NO
)
2
Gas category 3+: General
Orifice diameter
(1) = Blank plate
(2) = Burner pressure regulator
(3) = High-low control
Gas category G30 - 30 mbar
Nominal load (gross calorific value)
Nominal output
Supply pressure
(†)
Burner pressure
(*)
Gas consumption
Gas category G31 - 37 mbar
Nominal load (gross calorific value)
Nominal output
Supply pressure
(†)
Burner pressure
(*)
Gas consumption
(*) Based on 1013.25 mbar and 15 °C.
(†) If using a blank plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to the supply pressure. In practice, however, the burner pressure will be lower.
Unit
ADM 40
ADM 50
mm
3.20
3.20
1, 2 or 3
2
2
kW
42.2
56.5
kW
32.3
42.8
mbar
20
20
mbar
8.5
8.5
3
m
/h
4.0
5.4
mg/kWh
mg/kw
240
235
mm
1.70
1.70
1, 2 or 3
1
1
kW
41.6
55.3
kW
32.6
42.8
mbar
30
30
mbar
-
-
kg/h
3.0
4.0
kW
38.4
51.1
kW
30.0
39.5
mbar
37
37
mbar
-
-
kg/h
2.7
3.7
ADM 60
ADM 80
ADM 90
3.10
2.95
3.20
2
2
2
66.4
82.5
98.3
50.2
62.4
74.3
20
20
20
8.5
8.5
8.5
6.3
7.9
9.4
235
229
283
1.70
1.50
1.70
1
1
1
68.2
80.7
96.1
52.8
62.6
74.5
30
30
30
-
-
-
5.0
5.9
7.0
63.3
77.7
89.6
48.9
60.1
69.2
37
37
37
-
-
-
4.5
5.6
6.4
ADM 115
ADM 135
3.20
3.90
2
2
126.6
143.4
95.8
109.8
20
20
8.5
11.3
12.1
13.7
311
276
1.70
2.25
1
3
123.5
138.4
95.8
108.5
30
30
-
-
9.0
10.1
113.0
130.1
87.4
101.7
37
37
-
-
8.1
9.3

Advertisement