Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
Bat Fail
is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes.
NC, C, NO
Battery reconnection is reported within 1 minute (power-limited) (Figure 2 - 1b).
– BAT +
Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Figure 2 - 1g).
Terminal Identification:
Power Distribution Module
Terminal Legend
Function/Description
1P to 8P
Positive DC power outputs
1N to 8N
Negative DC power outputs
Figure 2 - PS161-6 Board configuration
5A 250V
L
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED
to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail
relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local
annunciation.