Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1 and with all
local codes and authorities having jurisdiction. The product must be located indoors within the protected premises.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two
upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the two upper screws,
level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place
the enclosure's upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure
Dimensions, pg. 8).
2. Secure enclosure to earth ground.
3. Set the DC output voltage to 24DC by setting SW1 to the open position on the power supply board (Figure 2-1a).
4. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Figure 1). Use 18 AWG for all power connections and 18 AWG
to 22 AWG for power limited circuits (AC Fail/Low Battery reporting). Secure green wire lead to earth ground. Keep power-limited wiring
separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires). Minimum 0.25" spacing must be provided.
5. Measure output voltage before connecting devices. This helps avoid potential damage.
6. Connect the delayed egress exit device locking hardware positive leads to terminals marked 1 through 4 POS (+) on the PD8ULCB board
and negative leads to the NEG 1 terminals through 4 terminals.
Figure 1 - Wiring Diagram for Connecting DE Exit Devices to a PS161-6 Power Supply
Separation of power-
limited wiring from
non power-limited
Green Lead
wiring must be at
(Ground)
least 1/4 inch.
N.C. Input
from
Fire Panel
10K EOL
N.O. Input
from
Fire Panel
10K EOL
No Fire
Connections
10K EOL
OR
OR
Power-limited
Note
A 10k EOL (End of Line) Resistor must be installed across terminals marked (Trigger EOL Supervised) on the PS161-6 board or the
unit will remain in fire alarm condition.
7. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage.
Batteries must be lead acid or gel type if used. Use two 12VDC batteries connected in series for 24VDC operation (Battery leads included).
8. Connect battery to terminals marked [-- BAT + ] (Figure 2 - 1g). Use two (2) 12VDC batteries connected in series for 24VDC operation
(battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH)
batteries or UL recognized BAZR2 batteries of an appropriate rating.
9. To trigger the power supply from a fire alarm control panel (FACP), connect signaling circuit of FACP to terminals marked Trigger End of
Line Supervised.
10. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Figure 2 - 1c).
11. To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Figure 2 - 1c).
Note
Must be set to ON position for Burglar Alarm Applications.
5A 250V
Power must be
turned off
L
before changing
120VAC Power Mains
G
the voltage
(Non Power-limited)
select switch.
Switch Detail
AC1
Open - 24V
NC
Battery & AC
C
Closed - 12V
NO
Supervision Circuit
NC
(Power-limited)
C
NO
Open - 24V
Closed - 12V
AC
Potentiometer
DC
AC DELAY
SHUTDOWN
Battery
Connections
(Non
Power-limited)
--- BAT +
--- DC
+
DC Output to Devices
(1P-8P Power Outputs)
(1N-8N Common Outputs)
Divider
12VDC Rechargeable
Battery
2/9
From Power Supply Board
(Factory Installed)
Delayed Egress
Exit Device #4
Delayed Egress
Exit Device #3
Delayed Egress
Exit Device #2
Delayed Egress
Exit Device #1
+
+
12VDC Rechargeable
Battery
02140-11-E Copyright
Stanley Security, Inc. 2014
©