Haier AW07LC2VHA Technical Overview page 30

Hide thumbs Also See for AW07LC2VHA:
Table of Contents

Advertisement

Outdoor Unit Pressure Switch Error Codes
There are two pressure switches in the outdoor unit, a low pressure switch and a high pressure switch. They connect to the
ECU via plugs CN-12 and CN-13. The low pressure switch is connected at CN-12 and the high pressure switch at CN-13. A low
pressure error will generate an Error Code 44. A high pressure error will generate an Error Code 45.
Low
Pressure
Switch
Testing Procedure
If the system generates one of these codes, it is very unlikely that the switch is actually bad, it is much more likely that the
refrigeration system pressures are either too high or too low. The vapor line connection can be used to measure the high pres-
sure during heating mode operation and low pressure during cooling mode operation.
There are no pressure ports that can be accessed to measure low pressure in heat mode nor high pressure in cool mode. If the
system trips on one of these errors where pressure cannot be measured, it is going to be necessary to remove system charge
and re-charge to confirm low or high charge is not causing the problem.
Error Code 43 or 45
This code is indicating that system pressure is too low. Refer
to the detailed information on sensor responses for more
information.
Typical Causes of Low Pressure Cool Mode
Lack of charge (hot compressor)
Low Heat on Indoor Coil (Cool Compressor)
Restriction (Not likely)
Typical Causes of Low Pressure Heat Mode
Cold outdoor air (Running system in very cold air.)
Lack of charge (Hot Compressor and Indoor Coil)
Restriction (Not Likely)
Error Code 42 or 44
The system is operating at excessive refrigerant pressure. If
the system is a new installation, it is likely that the charge is
too high. Refer to the reference section for installation and
charging procedure. (Note the Weight Method is the ONLY
way to charge this system. )
PAGE 30
OUTDOOR UNIT ERROR CODES
Pressure Switch Error Codes
Typical Causes of High Pressure In Cool Mode
Typical Causes of High Pressure In Heat Mode
Note: If the refrigerant pressures are correct, yet the system
does not close the error reporting pressure switch, replace
the defective pressure switch.
ERROR CODES
Overcharge
Dirty Outdoor Coil
Restriction (Not Likely)
Overcharge
Undersized Refrigerant Lines/Exceeding Length
Restriction (Not Likely)
High
Pressure
Switch

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents