Selection Of Location For Installation - Mitsubishi SRK25ZD-S Technical Manual

Inverter wall mounted type room air-conditioner
Table of Contents

Advertisement

5.1 Selection of location for installation

(1) Indoor unit
(a)
Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
(b)
A solid place where the unit or the wall will not vibrate.
(c)
A place where there will be enough space for servicing. (Where
space mentioned below can be secured)
(d)
Where wiring and the piping work will be easy to conduct.
(e)
The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
(2) Outdoor unit
(a)
A place where good air circulation can be obtained.
(b)
A place where the exhausted air will not be sucked in for the second time.
(c)
A place where the unit will not be affected by other heat sources. (When there are several units installed or another heat
source)
(d)
Do not install the unit near the seaside, or where there is possibility of chlorine gas generation.
(e)
A place where discharged hot and cold air or unit's operating sound will not be a nuisance to the neighborhood.
(f)
A place where servicing space can be secured.
100
Note (1) If the wall is higher than 1.2 m or a ceiling is
present, distances larger than indicated in the above
table must be provided.
(g)
A place where vibration will not be enlarged.
(h)
In heating operation, snow deposit on the heat-exchanger of outdoor unit must be
prevented for keeping the normal performance capacity.
(i)
Snow-hood on outdoor unit as in drawing, will reduce the frequency of
defrost operation.
When installing the snow hood, take care so that the air outlet of the snow
hood will not face directly into the most windy direction.
(ii) Design the base higher than possible snow deposit.
(3) Limitations for one way piping length and vertical
height difference.
Item
One way piping length (R)
Outdoor
Vertical
unit is lower
height
Outdoor unit
difference (H)
is higher
Unit : mm
Air inlet
No obstacles
(Service space
for electrical
parts)
Air
Outlet
Model
SRK25ZD-S
SRK35ZD-S
15 m
10 m
10 m
5 cm
SRK50ZD-S
25 m
15 m
15 m
26
-
-
6.5 cm
1.5 cm
Snow hood
Height:
Must be over
the possible
snow deposit
height
h
10 cm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35zd-sSrk50zd-sl

Table of Contents