Heatilator CD4236IR-D Owner's Manual page 71

Table of Contents

Advertisement

15 in.
(381 mm)
1 in.
(25 mm)
14 in.
(356 mm)
3/8 in. (10 mm)
1 in. (25 mm)
Figure 16.13 Vent Components
Heatilator • CD4236IR-D, CD4236ILR-D, CD4842IR-D, CD4842ILR-D • 2359-900 Rev. D • 5/15
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-
SS termination cap on top vented fi replaces,
a one foot minimum vertical vent section is
required before installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented
fi replaces, a three foot minimum vertical vent section is
required before installing fi rst elbow.
8-1/8 in.
13 in.
(206 mm)
(330 mm)
HORIZONTAL TERMINATION CAP
7-1/4 in.
(184 mm)
7-3/4 to 10-3/8 in.
(197 to 264 mm)
DVP-FBHT
FireBrickTermination Cap
WARNING
Effective Length
5-3/4 to 8-3/8 in.
5-1/2 in.
146 to 213 mm
140 mm
87°
SLP-HRC-SS
SLP-HRC-ZC-SS
2-3/4 in.
(70 mm)
12-1/4 in.
(311 mm)
16 in.
(406 mm)
(For use with IPI and DSI appliances only. Must use PVK80-PLUS Kit)
C
D
LDS33/LDS46 Decorative Shroud
A
Catalog #
in.
LDS33
36
LDS46
48
8-3/8 in.
213 mm
10-1/2 in.
267 mm
10-7/8 in.
276 mm
9 in.
(229 mm)
11-1/2 in.
(292 mm)
PVK-80
B
A
B
C
mm
in.
mm
in.
mm
914
36
914
8.5
216
1219
72
1829
8.5
216
12-1/2 in.
(318 mm)
D
in.
mm
11
279
11
279
71