FITZROY (Sub 1.0) FREESTANDING WOODBURNER
A. Yunca recommends that competent trades persons carry out all installations (e.g. NZHHA
Registered Installer), to obtain maximum performance and safe, efficient heating.
B. A permit is required and we suggest you check with local building inspectors as by-laws do
vary from area to area.
Also notify your Insurance Company that a solid fuel heater has been installed.
C. Floor Protector –
1. Must extend a minimum of 300mm in front of the door aperture.
2. Must extend at least 100mm from each side of the heater.
3. Ash Floor Protector must be constructed of non-combustible materials, with a
minimum thickness of 12mm
D. Seismic restraint – Heater must be restrained from seismic movement as required by AS/NZS
2918:2001. 10mm diameter bolting holes in the feet of the FITZROY allow restraint.
E. Manufacturers' recommended tested minimum clearances from combustible walls:
Tested to AS/NZS 2918 : 2001 by APPLIED RESEARCH SERVICES
Rear Clearance – from rear of top lip
Side Clearance (with YUNCA flue mounted shield fitted)
Corner Clearance (with YUNCA flue mounted shield fitted)
F. YUNCA Flue Kit (Tested to AS/NZS 2918:2001 Appendix F): Fig A, B & E
1. 4.2m x 150mm stainless steel flue
2. 2.4m x 250mm galvanised liner.
3. 1 x ceiling tile.
Please Note: All flue joints must be sealed with flue sealing compound. Use stainless steel
screws or rivets to join the flue pipe (three equally spaced places at each joint). The first
length of flue pipe must be screwed to flue spigot. The required minimum flue termination
height is 4.6 m above the floor protector.
G. FITZROY Sub 1.0 Flue Mounted Shield (Flue Guard) Kit.
Complies (with heater) to AS/NZS 2918:2001: Refer Fig A.
1 x 1200mm length lined back guard plus an adjustable 900mm extension.
1 x 1200mm length perforated front guard
1 x 1200mm length tertiary back guard with spacer tabs.
1 x Top front deflector shield (half round shape, angled 30 degrees when installed).
Please Note: The minimum Flue Mounted Shield height Is 1200mm.
Fitzroy Install NOV 2010
A division of Terry Young Ltd , New Zealand
INSTALLATION INSTRUCTIONS for
NOVEMBER 2010
TESTED in compliance with AS/NZS 2918: 2001
- N.B. clearance from rear panel is 120mm
(with YUNCA flue mounted shield fitted)
4. 1 x insulation boundary shield.
5. 2 x spider brackets.
6. 1 x weather cap & cowl.
www.yunca.co.nz
Clearance
100 mm
300 mm
130 mm
Page 1 of 4

Advertisement

loading

Summary of Contents for Yunca Gas fitzroy

  • Page 1 12mm D. Seismic restraint – Heater must be restrained from seismic movement as required by AS/NZS 2918:2001. 10mm diameter bolting holes in the feet of the FITZROY allow restraint. E. Manufacturers’ recommended tested minimum clearances from combustible walls:...
  • Page 2 FITZROY SUB 1.0 – TYPICAL INSTALLATION (not drawn to scale) FIG A (below, left): FITZROY Sub 1.0 Flue Mounted Shield (Flue Guard) Kit. Complies (with heater) to AS/NZS 2918:2001 TOP CAP (Fits inside flue) ENLARGEMENT OF CEILING ASSEMBLY FIG B 25mm min.
  • Page 3 FIG C: HEATER DIMENSIONS – Fitzroy (Drawings on this page not drawn to scale) Ash Floor Protector FIG D: HEATER POSITION. * N.B. Measurement “A” is taken from the top lip at the rear of the fire. Above: Non combustible wall clearances. Brick lining from floor to within 25mm of ceiling.
  • Page 4: Important Information

    INSTALLATION UNSAFE. IF A WATERBOOSTER IS FITTED: NOTE: A WATER BOOSTER CANNOT BE FITTED TO THE FITZROY (SUB 1.0) CLEAN AIR MODEL A. DO NOT CONNECT TO AN UNVENTED HOT WATER SYSTEM B. INSTALL IN ACCORDANCE WITH AS 3500.4.1 OR NZS 4603 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODES.