Connecting (Power and Control Cable)
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied
connecting cable from the outdoor unit to indoor unit consists of
three (3) wires and provides the power for the indoor unit. Two
wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National
Electrical Code) or CEC (Canadian Electrical Code) for special
requirements.
All wires must be sized per NEC or CEC and local codes. Use
Electrical Data table MCA (minimum circuit amps) and MOCP
(maximum over current protection) to correctly size the wires and
the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt
rating and 2/64- -inch thick insulation must be used.
Control Wiring:
A separate shielded copper conductor only, with a minimum 300
volt rating and 2/64- -inch thick insulation, must be used as the
communication wire from from the outdoor unit to the indoor unit.
To minimize voltage drop of the control wire, use the following
wire size and maximum lengths shown in the chart below.
Wire Size
18 AWG
16 AWG
Electrical Data
System Voltage
Unit Size
Volts--- Ph.--- Freq.
9K--- AC
115--- 1--- 60
9K--- HP
115--- 1--- 60
12K--- AC
115--- 1--- 60
12K--- HP
115--- 1--- 60
12K
208/230--- 1--- 60
18K
208/230--- 1--- 60
24K
208/230--- 1--- 60
30K
208/230--- 1--- 60
36K--- AC
208/230--- 1--- 60
36K--- HP
208/230--- 1--- 60
Length
ft (m)
50 ft. (15 m)
50 ft (15) to 100 ft. (30 m)
Operating
Compressor
Voltage
RLA
LRA
(Min/Max)
103/127
9.76
25
115 AC
103/127
9.76
20
176--- 375 DC
103/127
11.20
25
115 AC
103/127
11.20
20
176--- 375 DC
187/253
7.30
16.5
208/230 AC
187/253
10.86
27
208/230 AC
187/253
11.71
41
208/230 AC
187/253
13.45
40
310 DC
187/253
16.92
67
310 DC
187/253
17.50
67
310 DC
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 300 volt .
rating and 2/64 inch thick insulation.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction.
A fire hazard may also exist. Therefore, be sure all
wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
Outdoor Fan
Output
Volts
FLA
Watts
0.17
30
0.17
30
0.17
30
0.17
30
0.25
21
208/230 V--- AC
0.62
60
208/230 V--- AC
0.62
60
208/230 V--- AC
0.45
100
208/230 V--- AC
0.73
100
208/230 V--- AC
0.73
170
208/230 V--- AC
3
CAUTION
CAUTION
Indoor Fan
Output
Volts
FLA
Watts
115 V--- AC
0.38
15.0
115 V--- AC
0.38
15.0
115 V--- AC
0.38
15.0
115 V--- AC
0.38
15.0
0.19
15.0
0.32
20.0
0.45
35.0
0.40
40.0
0.47
60.0
0.47
60.0
Max
Fuse/CB
MCA
Amps
(MOCP)
13
20
13
20
15
25
15
25
10
15
15
25
16
25
20
30
24
35
24
40