Installation; Pre-Installation; Transporting And Unpacking The Unit; Examining The Unit - Lochinvar Lock Temp SJS060 Installation & Operation Manual

Table of Contents

Advertisement

2

Installation

Pre-Installation

1.
The installation must conform to the instructions
in this manual and all applicable local, state,
provincial, and national codes, laws, regulations, and
ordinances. Installations in Canada must conform to
B149.2 Installation Code.
2.
Be certain the domestic water supply to the tank has
physical and chemical characteristics that fall within
the limits shown in Table 2A. Where questions exist
as to the composition of the water on the job, a
qualified water treatment expert should be consulted.
Water with characteristics outside the
CAUTION
limits shown in Table 2A may severely
shorten the life of the tank due to
corrosion. Damage to tanks in such
cases is not covered under warranty.
3.
Read and understand all installation requirements in
this manual.
Table 2A
Water Chemistry Requirements
Water used in the tank must have characteristics falling
within the following limits:
Characteristic
Min.
Ph
Chloride (PPM)
Transporting and unpacking the
unit
Each jacketed Lochinvar SJS Storage Tank is cartoned as
necessary at the factory. The carton is designed to provide
protection for the unit during transportation, and to
provide a safe means by which to lift and move the unit
with a fork lift or hand truck.
Max.
6.0
8.0
--
80
®
Installation and Operation Manual

Examining the unit

After the unit has been uncartoned and set in place, it should
be carefully examined to assure the tank has not been damaged
during shipping. If any evidence of damage is detected that
could affect the safe operation of the unit, contact Lochinvar
, LLC., or your authorized sales representative, to report the
damage and to receive instructions on how to proceed.
After the unit and all components have been inspected for
damage, it is suggested that all optional or independent
pressure and temperature control components be checked
to assure that they meet or exceed design specifications.
If any discrepancy is found, contact Lochinvar, LLC., or
your authorized representative, before proceeding with the
installation.

Anchoring the unit

The unit should be anchored to the floor, following applicable
architectural / local code requirements, or accepted standards
for the specific installation site. The unit should be installed
in a location with sufficient clearance for service and repair.
Check local codes for Seismic anchoring requirements. If
further assistance is needed, call the Lochinvar Technical
Service Department and request a Seismic Report.
Recommended clearances
The installation location must provide adequate clearances for
servicing and proper operation of the tank. A 12 inch vertical
clearance is recommended from the top of the tank. A zero
clearance is allowed for the sides of the tank.

Locating the tank

The appliance MUST be located where
CAUTION
leakage from the relief valve, leakage from
related piping, or leakage from the tank
or connections, will not result in damage
to the surrounding areas, or to the lower
floors of the building. A hot water storage
tank should always be located in an area
with a floor drain or installed in a drain pan
suitable for water heaters. The manufacturer
shall not be held liable for any such water
damage.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lock temp sjs080Lock temp sjs119

Table of Contents