★ flash at 5Hz,  light,
12.2 Outdoor unit error code explanation:
Display
E0
Outdoor EEPROM malfunction
E2
Indoor / outdoor units communication error
E3
Communication malfunction between IPM board and outdoor main board
E4
Open or short circuit of outdoor unit temperature sensor
E5
Voltage protection
E8
Outdoor fan speed has been out of control
F1
No A Indoor unit coil outlet temperature sensor or connector of sensor is defective
F2
No B Indoor unit coil outlet temperature sensor or connector of sensor is defective
F3
No C Indoor unit coil outlet temperature sensor or connector of sensor is defective
F4
No D Indoor unit coil outlet temperature sensor or connector of sensor is defective
F5
No E Indoor unit coil outlet temperature sensor or connector of sensor is defective
High pressure protection (For 38QUS036DS4)
P1
P2
Low pressure protection (For 38QUS036DS4)
P3
Current protection of compressor
P4
Temperature protection of compressor discharge
P5
High temperature protection of condenser
P6
IPM module protection
Note: Once these error codes display, they will disappear in at least 30 seconds if the unit come back to
normal.(Except E3&E4)
X
Indoor / outdoor units communication error
X
Indoor EEPROM malfunction
IPM module protection
Open or short circuit of T3 or T4 temperature sensor
Outdoor unit voltage protection
Outdoor unit over-current protection
X
Top temperature protection of compressor
X
Inverter compressor drive protection
Mode conflict
Indoor fan speed has been out of control
Outdoor fan malfunction
flash at 0.5Hz, X extinguished
LED STATUS