Sharp R-310B Service Manual page 12

Table of Contents

Advertisement

R-310B
PROCEDURE
LETTER
indicated in both direction then the asymmetric rectifier is good. If an asymmetric rectifier is shorted
in either direction, then the asymmetric rectifier is probably faulty and must be replaced with high
voltage rectifier. When the asymmetric rectifier is defective, check whether magnetron, high voltage
rectifier, high voltage wire or filament winding of the power transformer is shorted.
CARRY OUT 4R CHECKS.
NOTE: FOR MEASUREMENT OF THE RESISTANCE OF THE RECTIFIER, THE BATTERIES OF THE
MEASURING INSTRUMENT MUST HAVE A VOLTAGE AT LEAST 6 VOLTS, BECAUSE
OTHERWISE AN INFINITE RESISTANCE MIGHT BE SHOWN IN BOTH DIRECTIONS.
D
HIGH VOLTAGE CAPACITOR TEST
CARRY OUT 3D CHECKS.
A. Isolate the high voltage capacitor from the circuit.
B. Continuity check must be carried out with measuring instrument which is set to the highest resistance
range.
C. A normal capacitor shows continuity for a short time (kick) and then a resistance of about 10MΩ after
it has been charged.
D. A short-circuited capacitor shows continuity all the time.
E. An open capacitor constantly shows a resistance about 10 MΩ because of its internal 10MΩ resistance.
F. When the internal wire is opened in the high voltage capacitor shows an infinite resistance.
G. The resistance across all the terminals and the chassis must be infinite when the capacitor is normal.
If incorrect reading are obtained, the high voltage capacitor must be replaced.
CARRY OUT 4R CHECKS.
E
SWITCH TEST
CARRY OUT 3D CHECKS.
Isolate the switch to be tested and using an ohmmeter check between the terminals as described in the
following table.
Plunger Operation
Released
Depressed
If incorrect readings are obtained, make the necessary switch adjustment or replace the switch.
CARRY OUT 4R CHECKS.
F
TEMPERATURE FUSE AND THERMAL CUT-OUT TEST
CARRY OUT 3D CHECKS.
Disconnect the leads from the terminals of the temperature fuse or thermal cut-out. Then using an
ohmmeter, make a continuity test across the two terminals as described in the table below.
CARRY OUT 4R CHECKS.
Parts Name
Thermal cut-out 125˚C
Thermal cut-out 95˚C
If incorrect readings are obtained, replace the temperature fuse or thermal cut-out.
An open circuit thermal cut-out 95˚C (MG) indicates that the magnetron has overheated, this may be
due to resistricted ventilation, cooling fan failure or a fault condition within the magnetron or HV circuit.
An open circuit thermal cut-out 125˚C (OVEN) indicates that the foods in the oven may catch fire, this
may be due to over heating produced by improper setting of the cooking time or failure of the control
panel.
TEST PROCEDURES
Table: Terminal Connection of Switch
COM to NO
Open circuit
Short circuit
Table: Temperature fuse and Thermal cut-out Test
Temperature of "ON" condition
(closed circuit) (˚C)
This is not resetable type.
Below 75˚C
10
COMPONENT TEST
COM to NC
COM; Common terminal
Short circuit
NO;
Open circuit
NC;
Temperature of "OFF" condition
(open circuit) (˚C)
Above 125˚C
Above 95˚C
Normally open terminal
Normally close terminal
Indication ofohmmeter
(When room temperature
is approx. 20˚C)
Closed circuit.
Closed circuit.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents