Start-Up; General Information; Description Of Functions; Heat Pump Remote Control - Dimplex LAS 10MT Installation And Operating Instructions Manual

Air-to-water heat pumps for swimming pool heating (outdoor installation)

Advertisement

Available languages

Available languages

7
7

Start-Up

7.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorized by the
manufacturer. Only then can an extended warranty period of
3 years in total be granted (see Warranty Service).
7.2 Start-Up
The following items need to be checked prior to start-up:
The heat pump must be fully connected, as described in
Chapter 6.
Any valves that might impair proper water flow in the water
circuit must be opened.
The air intake and air outlet paths must be clear.
The ventilator must turn in the direction indicated by the ar-
row.
The remote control must be operational.
Ensure the condensate outflow functions.
After connecting the operating voltage and switching on the
swimming pool heat pump, there will be a pre-programmed
5-minute compressor pause time before the heat pump
starts up.
The bypass and regulator valves must be set so that the
minimum water flow is in accordance with the Device Infor-
mation. The following maximum temperature spreads be-
tween water inlet and water outlet are set for the operating
point.
External air tempera-
ture
between water inlet and water
From
To
18° C
20° C
15° C
18° C
E-6
Max. temperature spread
outlet
6-7 K
5-6 K
8

Description of Functions

8.1 Heat Pump Remote Control

The heat pump can be switched on and off inside the building
(Frost-free and dry) via the remote control. The heat pump is op-
erational at water temperatures <10°C. In order to ensure frost
protection, continuous operation of the filter pump must be en-
sured on-site when there is a danger of frost. This can be imple-
mented by using a frost protection thermostat, for example. The
temperature of the swimming pool water is adjusted via the ad-
justable transformer on the remote control.
The water temperature operating limits are between +10°C and
+40°C.
1)
Switch on / off
2)
The green LED lights up independent of the switch position
(indicating the heat pump is operationally ready)
3)
Has no function
4)
Setpoint regulator for water temperature
Position max. (right-hand stop), hot water set temperature:
40 °C.
Position min. (left-hand stop), hot water set temperature: 10 °C.
The setting knob has two setting rings for mechanically limiting
the setting range. (Note: before adjusting the setting rings, the
setting knob must be set to the approximate middle of the desired
setting range.)