Optional Connector Specifications Of Hot Water Module P.c. Board - Toshiba MMW-AP0271LQ-E Service Manual

Hot water module
Hide thumbs Also See for MMW-AP0271LQ-E:
Table of Contents

Advertisement

7-2. Optional connector specifications of hot water module P.C. board

Function
Connector No. Pin No.
HA
CN61
Option output
(*1)
CN60
External error
input
CN80
CHK
Operation
CN71
check
DISP
Display mode
CN72
(*1) For hot water module, terminal block of option output (CN 60) is equipped in the hot water module.
Refer to 3. WIRING DIAGRAM.
Specification
Start / stop input
1
2
0 V (COM)
Remote controller
3
disabling input
4
In-operation output
5
DC12 V (COM)
6
Alarm output
1
DC12V(COM)
2
Defrosting output
3
Heater output
4
Heating thermostat
5
output
6
Pump output
1
DC12 V (COM)
2
DC12 V (COM)
3
External error input
1
Check mode input
0 V
2
1
Display mode input
2
Display mode input
– 20 –
Remarks
Start / stop input for HA (J01: In place / Removed =
Pulse input (factory default) / Step input)
Enables / disables start / stop control via remote
controller
ON during operation (HA answerback signal)
ON while alarm ON
ON while outdoor unit ON
ON while heating thermostat ON (compresor ON)
Generates test code L30 and automatically shuts down
air conditioner (only if condition persists
for 1 minute)
Used for hot water module operation check (prescribed
operational status output, such as indoor PMV ON,
to be generated without communication with outdoor
unit or remote controller)
Product display mode - Communication just between
hot water module and remote controller enabled (upon
turning on of power) Timer short-circuited out (always)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmw-ap0561lq-eMmw-ap0271lq-trMmw-ap0561lq-tr

Table of Contents