Table 23 — Fan Performance 50HJQ006 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
0.1
(Cfm)
Rpm
Bhp
1500
658
0.27
1600
693
0.32
1700
729
0.38
1800
765
0.45
1900
802
0.52
2000
840
0.60
2100
878
0.69
2200
916
0.78
2300
954
0.89
2400
993
1.00
2500
1031
1.13
AIRFLOW
1.0
(Cfm)
Rpm
Bhp
1500
1108
0.90
1600
1130
0.97
1700
1154
1.06
1800
1178
1.14
1900
1201
1.23
2000
1226
1.33
2100
1252
1.45
1280
1.58
2200
2300
1309
1.71
2400
1336
1.80
2500
1363
2.00
LEGEND
— Brake Horsepower Input to Fan
Bhp
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1020 to 1460 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
EXTERNAL STATIC PRESSURE (in. wg)
0.2
Watts
Rpm
Bhp
Watts
276
722
0.33
337
327
754
0.38
388
388
787
0.44
450
460
821
0.51
521
531
854
0.58
593
613
900
0.66
674
705
923
0.75
766
797
958
0.85
869
910
993
0.96
981
1022
1029
1.07
1093
1155
1066
1.20
1226
EXTERNAL STATIC PRESSURE (in. wg)
1.2
Watts
Rpm
Bhp
Watts
920
1186
1.08
1104
991
1205
1.15
1175
1083
1226
1.23
1257
1165
1249
1.32
1349
1257
1274
1.43
1461
1359
1297
1.53
1564
1482
1320
1.64
1676
1615
1345
1.77
1809
1747
1372
1.91
1952
1891
1400
2.06
2105
2044
1428
2.22
2269
0.4
Rpm
Bhp
Watts
Rpm
840
0.46
470
937
867
0.52
531
963
895
0.58
593
991
923
0.65
664
1019
953
0.73
746
1046
984
0.82
838
1073
1015
0.91
930
1101
1046
1.01
1032
1129
1079
1.13
1155
1160
1112
1.25
1277
1190
1145
1.39
1420
1220
1.4
Rpm
Bhp
Watts
Rpm
1263
1.30
1328
1343
1278
1.35
1380
1350
1296
1.42
1451
1364
1316
1.52
1553
1382
1338
1.62
1656
1402
1363
1.73
1768
1424
1388
1.80
1891
1448
1410
1.97
2013
1473
1434
2.11
2156
1496
1459
2.26
2310
1519
1486
2.43
2483
1543
3. Maximum usable watts input is 2120 and maximum continuous
bhp is 1.80 for single-phase units and 2.40 for 3-phase units.
Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not
result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. For additional information on motor
performance, refer to Tables 6 and 7.
4. Values include losses for filters, unit casing, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
29
0.6
0.8
Bhp
Watts
Rpm
Bhp
0.59
603
1027
0.74
0.65
664
1052
0.81
1075
0.88
0.73
746
0.81
828
1099
0.96
0.90
920
1126
1.06
0.99
1012
1154
1.16
1.08
1104
1182
1.27
1.19
1216
1209
1.39
1.31
1339
1237
1.51
1.43
1461
1264
1.63
1.57
1604
1292
1.77
1.6
1.8
Bhp
Watts
Rpm
Bhp
1.58
1615
1431
1.79
1.61
1645
1424
1.80
1.64
1676
1432
1.89
1.72
1758
1447
1.95
1.80
1870
1464
2.05
1.94
1983
1484
2.16
2.07
2115
1505
2.29
1529
2.43
2.20
2248
2.34
2391
1554
2.58
2.48
2534
1578
2.76
2.65
2708
1600
2.89
Watts
756
828
899
981
1083
1185
1298
1420
1543
1666
1809
Watts
1829
1921
1931
1993
2095
2207
2340
2483
2637
2820
2953