5. Slide the outdoor-air inlet screens into the screen track on
the hood side panels. While holding the screens in place,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen. Do not attach completed (Fig. 23) hood
assembly to unit at this time.
6. Slide the EconoMi$er assembly into the rooftop unit. See
Fig. 24 and 25.
NOTE: Be sure to engage rear EconoMi$er flange under tabs
in return air opening of the unit base. See Fig. 24.
7. Install the outdoor air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 25.
8. Remove and store the 12-pin jumper plug from the unit
wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagrams Fig. 26 and 27. Also refer to Fig. 28 if
installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure
using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 29.
11. Mount the supply-air temperature sensor to the lower left
portion of the indoor blower housing with the two (2)
screws provided (see Fig. 30). Connect the violet and
pink wires to the corresponding connections on the
supply-air temperature sensor. Replace the indoor fan
motor access panel.
OUTDOOR AIR
SEAL STRIP
OPENING
PANEL
SEAL STRIP
ASSEMBLED
EXHAUST HOOD
OUTDOOR AIR
HOOD SIDES
Fig. 22 — Outdoor-Air Hood Assembly
OUTDOOR AIR
HOOD TOP
WIRING
HARNESS
SCREEN
RETAINER
OUTDOOR AIR
INLET
SCREENS
15
Fig. 23 — Completed Hood Assembly
ECONOMIZER CLIP
UNIT FILTER
HVAC UNIT
RACK
UNIT BASE
Fig. 24 — Completed Hood Assembly
Fig. 25 — EconoMi$er Installed
ECONOMIZER
ECONOMIZER REAR
FLANGE
OUTDOOR
AIR
BLOCK-OFF
PLATE