Carrier 50HJQ004-007 Installation, Start-Up And Service Instructions Manual page 22

Single-package rooftop heat pump units
Table of Contents

Advertisement

Table 12 — Fan Performance 50HJQ005 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
0.1
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
542 0.16
168
1300
576 0.20
210
1400
610 0.24
252
1500
646 0.28
294
1600
681 0.33
347
1700
718 0.39
410
1800
754 0.45
473
1900
791 0.52
546
2000
828 0.60
630
AIRFLOW
1.0
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
1008 0.67
704 1052 0.73
1300
1029 0.75
788 1065 0.81
1400
1052 0.83
826 1087 0.90
1500
1076 0.91
905 1111 0.99
1600
1100 1.00
995 1134 1.08 1069 1168 1.15 1100 1232 1.31 1253 1291 1.46 1396 1350 1.60 1558
1700
1124 1.09 1084 1158 1.17 1164 1192 1.25 1196 1255 1.42 1358 1314 1.58 1511 1370 1.77 1738
1800
1147 1.18 1174 1182 1.27 1263 1217 1.36 1301 1279 1.54 1473 1381 1.71 1635 1393 1.89 1907
1900
1169 1.27 1263 1205 1.37 1363 1240 1.47 1406 1303 1.66 1588 1408 1.85 1769 1417 2.03 2068
2000
1194 1.38 1373 1228 1.48 1472 1262 1.58 1511 1327 1.78 1702 1436 1.98 1894 1440 2.18 2229
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 840 to 1185 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied motor drive is required.
2.
indicates field-supplied motor and drive are required.
3. Maximum usable watts input is 1000 and maximum continuous
bhp is 1.20. Extensive motor and electrical testing on these
Table 13 — Fan Performance 50HJQ005 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
0.2
(Cfm)
Rpm
Bhp
1200
618
0.21
1300
644
0.25
1400
673
0.30
1500
704
0.35
1600
736
0.40
1700
768
0.46
1800
801
0.52
1900
836
0.60
2000
870
0.68
AIRFLOW
1.2
(Cfm)
Rpm
Bhp
1096
0.78
1200
1300
1101
0.86
1400
1121
0.96
1500
1145
1.06
1600
1168
1.15
1700
1192
1.25
1800
1217
1.36
1900
1240
1.47
2000
1262
1.58
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.3
616 0.21
221
678 0.27
644 0.25
263
704 0.31
673 0.30
315
732 0.36
704 0.35
368
761 0.42
735 0.40
420
790 0.47
768 0.46
483
836 0.54
801 0.53
557
851 0.61
836 0.60
630
832 0.69
870 0.68
714
864 0.77
EXTERNAL STATIC PRESSURE (in. wg)
1.1
1.2
762 1096 0.78
846 1101 0.86
890 1121 0.96
980 1145 1.06 1014 1208 1.20 1138 1274 1.33 1272 1337 1.47 1350
EXTERNAL STATIC PRESSURE (in. wg)
0.4
Watts
Rpm
Bhp
Watts
263
739
0.32
378
315
764
0.37
441
378
791
0.42
504
441
818
0.48
578
515
845
0.54
662
599
873
0.81
757
693
900
0.69
851
788
928
0.77
967
904
968
0.86
1082
EXTERNAL STATIC PRESSURE (in. wg)
1.4
Watts
Rpm
Bhp
Watts
778
1134
0.89
935
935
1174
1.01
988
976
1183
1.09
1071
1081
1208
1.20
1215
1196
1232
1.31
1339
1310
1255
1.42
1463
1425
1279
1.54
1597
1559
1303
1.66
1731
1702
1372
1.78
1884
0.4
278
739 0.32
336
842 0.44
867 0.50
326
764 0.37
389
378
791 0.42
441
889 0.55
436
818 0.48
504
912 0.61
494
845 0.54
567
920 0.68
562
873 0.61
641
965 0.76
641
900 0.69
725
992 0.84
720
828 0.77
809
1019 0.93
809
858 0.86
904
1046 1.03 1053 1085 1.12 1139 1124 1.21 1237
1.4
820 1134 0.89
835 1203 1.00
904 1174 1.01 1040 1229 1.15 1100 1277 1.27 1029
918 1183 1.09 1042 1255 1.22 1167 1305 1.38 1190
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. For additional
information on motor performance, refer to Tables 6 and 7.
4. Values include losses for filters, unit casing, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
0.6
Rpm
Bhp
Watts
842
0.44
504
867
0.50
578
889
0.55
651
912
0.61
725
920
0.68
787
965
0.76
889
892
0.84
991
1019
0.93
1104
1046
1.03
1237
1.6
Rpm
Bhp
Watts
1203
1.00
965
1229
1.15
999
1255
1.22
1105
1274
1.33
1294
1291
1.46
1454
1314
1.58
1605
1381
1.71
1757
1408
1.85
1889
1436
1.98
2040
3. Values include losses for filters, unit casings, and wet coils. See
Table 8 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.4 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings
shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Tables 6 and 7.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
22
0.6
0.7
462
886 0.50
525
525
910 0.56
588
578
933 0.62
651
641
957 0.69
720 1001 0.76
695
931 0.76
772 1023 0.83
777 1005 0.84
853 1045 0.91
858 1032 0.92
940 1071 1.00 1022
950 1058 1.02 1037 1097 1.10 1124
1.6
1.8
885
0.8
Rpm
Bhp
Watts
Rpm
928
0.56
630
1008
952
0.62
704
1029
976
0.69
788
1052
1001
0.76
858
1076
1023
0.83
950
1100
1045
0.91
1063
1124
1071
1.00
1165
1147
1097
1.10
1277
1169
1124
1.21
1410
1194
1.8
Rpm
Bhp
Watts
Rpm
1232
1.07
1000
1258
1277
1.27
1029
1304
1305
1.38
1190
1333
1337
1.47
1350
1365
1350
1.60
1558
1379
1370
1.77
1738
1399
1383
1.89
1907
1423
1417
2.03
2068
1447
1440
2.18
2229
1471
0.8
929 0.56
588
952 0.62
651
976 0.69
725
777
848
930
1.0
Bhp
Watts
0.67
725
0.75
841
0.83
885
0.91
985
1.00
1084
1.09
1194
1.18
1313
1.27
1442
1.38
1572
2.0
Bhp
Watts
1.14
1083
1.35
1203
1.47
1367
1.57
1564
1.70
1805
1.89
2013
2.01
2210
2.16
2375
2.32
2551

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents