7-5 Test of new battery
Do the battery test when you exchange the battery. Check the connection of
the battery when BATTERY LED of UPS blinks every two seconds after
executing the test. Refer to the troubleshooting guide when the problem
continues.
・After the electrical discharge stops, when exchanging the battery with a new
full charge, the battery remainder capacity on management soft will be
correctly displayed after six hours. There is no influence in operation.
・The Battery test is done in only Standby, Online, HE Standby, OnHE. Refer the
section 4-3.
7-6 Recycling
Read "Attention for maintenance" about a correct abandonment method of
a used battery.
・Do not discard the batteries in the trash. This product contains sealed
・Do not discard the waste electrical or electronic equipment (WEEE) in the trash.
For proper disposal and more information, contact your local recycling/reuse or
hazardous waste center.
7-7 Fuse exchange
!
・Do the clearing work after confirming LED of UPS is not lighting with the input
cable pulled out. There is a possibility of the breakdown and the electric shock
when doing by the methods other than the following procedures.
Exchange fuses in the fuse box on the rear of UPS according to the
following procedures.
1. Remove the input cable of UPS from the power supply.
2. Confirm LED of UPS has been turned off.
3. Remove the lid of the fuse box on the back of UPS, and take out an
inside fuse.
4. Put a new fuse in the fuse box.
5. Turn and tighten the lid in the fuse box.
6. Connect the input cable of UPS with the power supply.
7. Confirm that UPS starts as usual.
47
lead-cid bateries and must be disposed of properly. For more
information, contact your local recycling/reuse or hazardous waste
center.
Attention
Attention
Attention