Mitsubishi 2033C SERIES Owner Technical Manual page 8

Uninterruptible power supply system
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
This UPS does not include an AC input circuit breaker (MCCB) to protect the
bypass and main input circuit. The AC input circuit breaker (MCCB) is to be field
supplied and installed. Circuit breaker (MCCB) specifications are as follows:
Capacity
(kVA)
7.5
10
15
20
30
40
50
AC output and DC input overcurrent protection and disconnection devices shall be field
supplied and installed.
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 2
AC input
Voltage (Vac)
208
208
208
208
208
208
208
MITSUBISHI ELECTRIC 2033C SERIES UPS
AC input
Recommended
Rating (Aac)
Breaker (A)
23
30
45
61
91
121
151