1.3 Overview

The UPS provides two power paths between the utility source and the critical load. Figure 1.1
shows the path for normal operation, with the load powered from the inverter. Figure 1.2 shows
the path for bypass operation, with the load supplied through the static bypass line.
FIGURE 1.1 Single Line Diagram - Normal Operation. Load powered by inverter.
CB
AC input
User
supplied
During normal operation, the path through the inverter is used to power the load.
Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is utilized to
charge the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to
clean AC power to supply the critical load.
The conversion - inversion process eliminates any voltage transients or fluctuations existing in the
input power before it reaches the critical load.
* The Input circuit breaker(MCCB) for protection of the UPS and cables are field supplied and field
installed. (See WARNING 2 in section 1.0).
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
CB3
CONVERTER
CB1
FI
BATTERY
MITSUBISHI ELECTRIC 2033C SERIES UPS
Static Transfer
Switch
INVERTER
52C
FO
FB
CB2
40kVA,
50kVA:
External Battery
Page Number:
1-5
Maintenance
Bypass
Switch
Output
52CS(7.5-20kVA)
52MB&52L(30-50kVA)
Power Flow
Not in Use
UPS Module