Parameter Description - Elektronikbau- und Vertriebs Ceta 100 Operating Manual

Differential temperature control
Table of Contents

Advertisement

BA_CETA100_EbV_EN_0450021000_0931-10.book Seite 6 Dienstag, 25. August 2009 3:33 15

Parameter description

5. Parameter description
01 Information level
Display
Designation
08:01
Heat capacity
08:02
Heat balance
08:03
Display pump
function
08:04
Temperature
Heat supplier
08:05
Temperature
Heat storage tank
08:06
Return temperature
08:07
Pump operating
hours
08:08
Pump starts
03 Parameter system
Display
Designation
03:01
Code entry
03:02
Automatic set
function
03:03
Bus address
03:06
Automatic exit time
6
Description
Current heat capacity in W
Display of cumulative heat energy in kWh
0: Pump is switched off
1: Pump is switched on
Sensor temperature of heat supplier (e.g. collector, solid fuel
boiler) at input F3
Sensor temperature of heat storage tank at input F1
Sensor temperature of return at input F2, if available.
Number of pump operating hours
Number of pump starts
Description
Setting range:
0 ... 999
Factory setting: 0
Function:
Show parameters marked with X3.
0=OFF, no automatic sensor detection
1=ON, automatic sensor detection
Setting range:
21...25
Factory setting: 21
Function:
If more than one CETA 100 or 101 has to be connected via data
bus within a system, each unit must be set to a unique address.
Setting range:
0.5 ... 10 min
Factory value:
0.5 min
Function:
When unit is not operated during the set time, the display
returns to basic display.
X1
X1
X3
X3
X3