Outdoor Coil, Indoor Coil, & Condensate Drain Pan; Outdoor Fan; Electrical Controls And Wiring - Bryant 577C Installation Instructions Manual

Preferred 14 seer single--packaged air conditionerand gas furnace system with puron (r--410a) refrigerant single and three phase 1-1/2-5 nominal tons (sizes 018--060)
Table of Contents

Advertisement

4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner rack to
the unit base (See Fig. 19).
8. Slide the burner rack out of the unit (See Fig. 19 and 22).
9. To reinstall, reverse the procedure outlined above.
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent and water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit. On
units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain trough is restricted, clear it with a
"plumbers snake" or similar probe device.
Flue
Collector
Inducer
Burner
Box
Blower
Rack
Housing
Fig. 19 - - Blower Housing and Flue Collector Box
Front
Access Panel
Fig. 20 - - Unit Access Panel
Integrated
Gas Unit
Controller
(IGC)
Auto Transformer
fuses used on 460
volt units only.
(Hidden)
Interface Fan
Board (IFB)
Induced Draft
Motor
Rollout
Switch
Mounting
Screw
A08045
A07151
Fig. 21 - - Removal of Motor and Blower Wheel
Fig. 22 - - Burner Rack Removed

Outdoor Fan

CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
1. Remove 6 screws holding outdoor grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off
motor shaft.
5. When replacing fan blade, position blade so that the hub is
1/8 in. (3.2 mm) away from the motor end (1/8 in. (3.2 mm)
of motor shaft will be visible).
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.

Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring.
Check all electrical connections for tightness. Tighten all screw
connections. If any smoky or burned connections are noticed,
disassemble the connection, clean all the parts, re- -strip the wire
end and reassemble the connection properly and securely.
29
BLOWER
HOUSING
2 SETSCREWS
(HIDDEN)
C99085
A07680

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents