Installation - Carrier MMU-AP0072H2UL Installation Manual

Table of Contents

Advertisement

4

Installation

REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use
buffering cloth or other soft cloth to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than
specified.
 External view
Ceiling bottom
surface
33.1" (840) Unit external dimension
Electrical control
Z
27.2" ± 0.8" (690 ± 20) Hanging bolt pitch
33.9" - 35.8" (860 - 910) Ceiling opening dimension
37.4" (950) Panel external dimension
Ceiling
bottom
surface
Knockout for
Auxiliary fresh air
flange
Z view
For Ø3.9" (100)
Ceiling bottom surface
Ceiling panel (sold separately)
Model MMU-
A
B
AP007 Type
10.1" (256)
Ø1/4" (6.4)
Ø3/8" (9.52)
AP009 Type
10.1" (256)
Ø1/4" (6.4)
Ø3/8" (9.52)
AP012 Type
10.1" (256)
Ø1/4" (6.4)
Ø3/8" (9.52)
AP015 Type
10.1" (256)
Ø1/4" (6.4)
Ø1/2" (12.7)
AP018 Type
10.1" (256)
Ø1/4" (6.4)
Ø1/2" (12.7)
9-EN
Ceiling bottom surface
6.8" (172)
Refrigerant
pipe
connecting
port (Liquid) B
Ceiling
Refrigerant
opening
pipe
dimension
connecting
16.1" (408)
port (Gas) C
1.6" (40)
Drain pipe
connecting
port
16.4" (416.5)
7.4" (189)
Hanging bolt 3/8" (M10)
(locally procured)
Unit: in (mm)
C
Model MMU-
A
B
AP021 Type
10.1" (256)
Ø3/8" (9.5)
Ø5/8" (15.9)
AP024 Type
10.1" (256)
Ø3/8" (9.5)
Ø5/8" (15.9)
AP030 Type
10.1" (256)
Ø3/8" (9.5)
Ø5/8" (15.9)
AP036 Type
12.6" (319)
Ø3/8" (9.5)
Ø5/8" (15.9)
AP042 Type
12.6" (319)
Ø3/8" (9.5)
Ø5/8" (15.9)
– 5 –
 Opening a ceiling and
installation of hanging bolts
• Consider the piping/wiring after the unit is hung to
determine the location of the indoor unit installation
and orientation.
• After the location of the indoor unit installation has
been determined, open the ceiling and install
hanging bolts.
• The dimensions of the ceiling opening and hanging
bolt pitches are given in the outline drawing and the
attached installation pattern.
• When a ceiling already exists, lay the drain pipe,
refrigerant pipe, control wires, and remote control
wires to their connection locations before hanging
Unit: in (mm)
the indoor unit.
Procure hanging bolts and nuts for installing the indoor
unit (these are not supplied).
4.4" (112)
Hanging bolt
2.3" (58)
Nut
1.7" (42)
Hole for power
supply wire
Using the installation pattern (accessory)
Conduit hole
The installation pattern is provided inside the
(knockout)
packaging cap.
Hole for remote
control wires
<For existing ceiling>
Use the installation pattern positioning a ceiling
opening and hanging bolts.
<For new ceiling>
Use the installation pattern to position the ceiling
opening when a ceiling is hanged.
• After the hanging bolts have been installed, install
the indoor unit.
• Hook the four holes in the installation pattern to the
Ceiling bottom
panel fixing screws of the indoor unit.
surface
• Before hanging a ceiling, open the ceiling along the
outside dimensions of the installation pattern.
Panel fixing
screw
C
hole
Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish
contractor.
In the process after the ceiling board has been
removed, it is important to reinforce ceiling foundation
(frame) and to keep horizontal level of installed ceiling
correctly in order to prevent vibration of ceiling board.
1. Cut and remove the ceiling foundation.
2. Reinforce the cut surface of ceiling foundation, and
add ceiling foundation for fixing the end of ceiling
board.
Installation of hanging bolt
Use 3/8" (M10) hanging bolts (4 pcs, locally procured).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
3/8" (M10)
4 pieces
Install the bolts with insert brackets or anchor bolts.
3/8" (M10)
12 pieces
(Blade type
bracket)
Use existing angles or install new support angles.
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Indoor unit
Installation pattern (Accessory)
New concrete slab
Rubber
Anchor bolt
(Slide type
(Pipe hanging
bracket)
anchor bolt)
Steel flame structure
Hanging bolt
Hanging bolt
Support angle
Existing concrete slab
10-EN