Note:1.The scale of concrete: cement : sand :macadam is 1:2:4, please put in ten φ10mm steel bar every 300mm spacing.
2.Must setting drain ditch around the foundation for drain all condensate that brought by outdoor unit.
3.The dimension C lie on installing location.
4.3 Space for installation of outdoor units
One single outdoor units can be installed in one place, many outdoors can be installed one big place, refer to the followings:
● Space for single unit
(1) Basic space required
(3) When there is an obstruction above the unit
≥ 45 °
Space for more than one units:
FRONT
BACK
BACK
FRONT
FRONT
BACK
≥ 600mm
4.4 Handling outdoor units
Please refer to the followings to conduct moving of units; To use 4 supporting point to move units instead of 3 points, to avoid unstable move
and units drop off;
Protective pads
>8m
Air Outlet Guide
Front
FRONT
BACK
BACK
FRONT
FRONT
BACK
Suspension ropes
(8m or longer × 2 ropes)
<40 °
>8m
>8m
(2) When inlet air enters from right and left sides of unit
(4) When unit is surrounded by walls
≥ 450mm
≥ 900mm
FRONT
FRONT
BACK
FRONT
FRONT
BACK
<40 °
>8m
≥ 900mm
≥ 450mm
FRONT
BACK
FRONT
FRONT
BACK