Dip Switch Settings; Jumper Selection - Secutron MR-2306-AT Wiring & Installation Manual

Remote annunciator
Hide thumbs Also See for MR-2306-AT:
Table of Contents

Advertisement

Introduction

Dip Switch Settings

Each annunciator needs to be assigned a unique, sequential address via DIP switches SW1-1, SW1-2, and SW1-3.
DIP switch SW1-4 is used to allow disabling of some front panel slide switches.
SW1-1
=
Address A0
SW1-2
=
Address A1
SW1-3
=
Address A2
When SW1-4 is "off", the System Reset and Signal Silence slide-switches are
always disabled, regardless of the operation of the keyswitch. The Buzzer
Silence and Lamp Test slide-switches will operate with the use of the
SW1-4
=
keyswitch.
When SW1-4 is "on", all four slide -switches on the front panel will operate
with the use of the keyswitch.
Set the annunciator address (see the manual for the fire alarm control panel being used), as follows in the table
below
Annunciator
Address
Notes:
Annunciators on a common RS-485 connection must be numbered sequentially; i.e.: 1,2,3,4, and not
randomly such as 5,3,7!! Note that not all Annunciator "Addresses" are valid for all Fire Alarm Control Panels.
Refer to the Fire Alarm Control Panel Manual for further information.

Jumper Selection

Jumper JP1 connects pins 1 and 2 and thus provides an eight bit checksum. The eight bit checksum is used for MR-
2300 Series Panel.
JW4 (Orange Wire)
Jumper Intact = Buzzer silence & Lamp Test local function only. System Reset & Signal Silence are disabled.
Cut Jumper (Orange Wire) to have all remote functions operate.
4
Three digit address of the annunciator (address
>
range 1 to 7 inclusive)
SW1-1
1
ON
2
OFF
3
ON
4
OFF
5
ON
6
OFF
7
ON
SW1 DIP Switch Settings
SW1-2
OFF
ON
ON
OFF
OFF
ON
ON
SW1-3
OFF
OFF
OFF
ON
ON
ON
ON