Troubleshooting Guide - Boyertown Furnace RSM 500 Installation, Operation And Maintenance Manual

Regal star series
Table of Contents

Advertisement

Troubleshooting Guide

WARNING
This equipment must be serviced, adjusted and started only by a qualified service
agency – an individual or agency, licensed and experienced with all codes and ordinances, and is
responsible for the installation and adjustment of the equipment.
Burner Goes Off on Safety
Oil T ank Full
Yes
Bleed Oil Lines
Oil flows Freely
Yes
Air in Oil Lines
No
Pump Pressure
l
Per Set-up Labe
Yes
Spark Established
Yes
Nozzle Clean and
Matches
Preliminary Settings
Yes
Air Settings Match
Preliminary
Settings
Yes
Refer to Burner
Manual for Control
T rouble Shooting
No
No
Yes
Check All Fitting
Connections
No
No
No
No
Fill T ank
No
Fuel Supply
Valves Open
Yes
No
Oil Filter Clean
Yes
No
Pump Strainer
Clean
No
Adjust Pressure
Per Set-up Label
Ignition Electrode
Yes
Shorted or
Cracked Porcelain
No
Open All
s
Supply Valve
Replace Oil
Filter
Clean or
Replace Strainer
Refer to Burner
Manual
Replace
Electrodes
Refer to Burner
Manual
Replace
Nozzle
Adjust Air
Settings
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rsm 600Rsm 750

Table of Contents