3-10. Electrical Service Guide For XMT 304 4-Racks

Input Voltage
Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1996 National Electrical Code (NEC).

3-11. Electrical Service Guide For XMT 304/EX 300 6-Racks

Input Voltage
Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1996 National Electrical Code (NEC).

3-12. Electrical Service Guide For XMT 456/Invision 456 Racks (Customer-Installed Only)

Input Voltage*
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
* Due to current demands, a rack containing XMT/Invisions 456 requiring 230/460 volt input power must be connected to 460 volt input power
only.
Reference: 1996 National Electrical Code (NEC).
230
460
200
110
2
6
210 (64)
301 (92)
6
6
230
460
300
175
1/0
2
215 (66)
451 (137)
4
6
460
200
2
210 (64)
6
575
90
8
300 (91)
8
S-0092J
575
125
4
467 (142)
6
S-0092J
575
175
2
451 (137)
8
S-0092J