PanelView Plus/VersaView CE Terminals and Display Modules
7. Alternately tighten the mounting clips screws to a torque of .90 - 1.1 N•m (8
- 10 in-lb). Do not over-tighten. Below are recommended torque sequences.
1
4 Clips
3
ATTENTION
!

Connecting DC Power

The PanelView Plus and VersaView CE terminals have an integrated power supply
that operates on 24V dc. The electrical input ratings of the power supply are:
• 24V dc nominal (18...32V dc)
• 70 Watts maximum (2.9A @24V dc)
The power supply is internally protected against reverse polarity.
The input power, terminal block on the power supply is removable and supports
the following wire sizes:
Wire Type
Stranded
Solid
Publication 2711P-IN001B-MU-P
4
1
6 Clips
2
4
Tighten the mounting clip screws to a torque of .90 - 1.1
N•m (8 - 10 in-lb) to provide a proper seal and to prevent
potential damage to the terminal. Allen-Bradley assumes no
responsibility for water or chemical damage to the terminal
or other equipment within the enclosure because of
improper installation.
Wire Size
#16 to #22 AWG
#18 to #22 AWG
5
3
2
6
Terminal Block Screw Torque
.23 - .45 N•m (2 - 4 in-lbs)
1
6
3
8 Clips
7
5
2
8
4