PanelView Plus/VersaView CE Terminals and Display Modules

Cutout Dimensions

The table below shows the overall cutout dimensions for each PanelView Plus and
VersaView CE terminal. Dimensions are in mm (inches).
Use the full size template shipped with your terminal to mark the cutout
dimensions.
PanelView Plus /VersaView CE Terminal
700/700H Keypad or Keypad & Touch
700/700H Touch
1000/1000H Keypad or Keypad & Touch
1000/1000H Touch
1250/1250H Keypad or Keypad & Touch
1250/1250H Touch
1500/1500H Keypad or Keypad & Touch
1500/1500H Touch

Installing Terminal in a Panel

All of the PanelView Plus and VersaView CE terminals are installed in the same
manner using clips for mounting. The number of clips used (4, 6 or 8) varies by
terminal type. The mounting clips are shipped with each terminal.
ATTENTION
!
To install terminal in a panel:
1. Cut an opening in the panel using the panel cutout provided with the
terminal. Remove any sharp edges or burrs.
2. Make sure the terminal sealing gasket is properly positioned on the terminal
as shown. This gasket forms a compression type seal. Do not use sealing
compounds.
Publication 2711P-IN001B-MU-P
• Disconnect all electrical power from the panel before
making the panel cutout.
• Make sure the area around the panel cutout is clear.
• Do not allow metal cuttings to enter any components
already installed in the panel.
• Failure to follow these instructions may result in personal
injury or damage to panel components.
Height
167 (6.57)
154 (6.08)
224 (8.8)
224 (8.8)
257 (10.11)
257 (10.11)
305 (12.00)
305 (12.00)
Width
264 (10.39)
220 (8.67)
375 (14.75)
305 (12.00)
390 (15.35)
338 (13.29)
419 (16.50)
391 (15.40)