Daikin FTXS60GV1B Service Manual page 99

Inverter pair wall mounted type
Hide thumbs Also See for FTXS60GV1B:
Table of Contents

Advertisement

SiBE041011EC
4.19.2 RK(X)S60F3V1B9, RXS60F4V1B
H0
Error Code
Method of Error
The system checks the DC current before the compressor starts.
Detection
Error Decision
Conditions
Supposed
Causes
Troubleshooting
Check the harness for the
compressor.
Turn off the power. Then, turn on
the power to restart the system.
Service Diagnosis
The voltage converted from the DC current before compressor start-up is out of the range
0.5 ~ 4.5 V.
The DC voltage before compressor start-up is below 50 V.
Broken or disconnected harness
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the harness broken?
NO
Restart operation
and error displayed
again?
YES
YES
NO
Troubleshooting
Replace the harness.
No problem.
Keep on running.
Replace the outdoor unit
PCB (main PCB).
(R21670)
88

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents